YVZ4V / NYBY

PVC Insulated Power Cables with Double Steel Tape Armour
Suitable for heavy-duty conditions where protection against external effects and mechanical strength are important. Thanks to its armored structure, it is resistant to impacts from outside. Resistant to sudden and short-term increases in working temperature. Used as a network and lighting cable, in cable ducts, under plaster, and underground.

Twisted
Technical Specifications
Product
1x10 mm²
13,5 mm
1,83 Ω/km
355,75 kg/km
A
Current Carrying Capacity in Air
64 A
Current Carrying Capacity in Ground
83 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x16 mm²
14,5 mm
1,15 Ω/km
436,58 kg/km
A
Current Carrying Capacity in Air
84 A
Current Carrying Capacity in Ground
107 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x25 mm²
16,2 mm
0,727 Ω/km
571,49 kg/km
A
Current Carrying Capacity in Air
114 A
Current Carrying Capacity in Ground
138 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x35 mm²
17,1 mm
0,524 Ω/km
682,59 kg/km
A
Current Carrying Capacity in Air
139 A
Current Carrying Capacity in Ground
164 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x50 mm²
18,8 mm
0,387 Ω/km
845,6 kg/km
A
Current Carrying Capacity in Air
169 A
Current Carrying Capacity in Ground
195 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x70 mm²
20,4 mm
0,268 Ω/km
1084,2 kg/km
A
Current Carrying Capacity in Air
213 A
Current Carrying Capacity in Ground
238 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x95 mm²
22,6 mm
0,198 Ω/km
1389,4 kg/km
A
Current Carrying Capacity in Air
264 A
Current Carrying Capacity in Ground
286 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x120 mm²
23,8 mm
0,153 Ω/km
1634,1 kg/km
A
Current Carrying Capacity in Air
307 A
Current Carrying Capacity in Ground
325 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x150 mm²
25,8 mm
0,124 Ω/km
1959,7 kg/km
A
Current Carrying Capacity in Air
352 A
Current Carrying Capacity in Ground
365 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x185 mm²
28,1 mm
0,0991 Ω/km
2382,5 kg/km
A
Current Carrying Capacity in Air
406 A
Current Carrying Capacity in Ground
413 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x240 mm²
31 mm
0,0754 Ω/km
3014,4 kg/km
A
Current Carrying Capacity in Air
483 A
Current Carrying Capacity in Ground
479 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x300 mm²
33,8 mm
0,0601 Ω/km
3657,6 kg/km
A
Current Carrying Capacity in Air
557 A
Current Carrying Capacity in Ground
541 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x10 mm²
19,5 mm
1,83 Ω/km
714,29 kg/km
A
Current Carrying Capacity in Air
59 A
Current Carrying Capacity in Ground
79 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x16 mm²
21,4 mm
1,15 Ω/km
905,27 kg/km
A
Current Carrying Capacity in Air
79 A
Current Carrying Capacity in Ground
102 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x25 mm²
24,9 mm
0,727 Ω/km
1251 kg/km
A
Current Carrying Capacity in Air
106 A
Current Carrying Capacity in Ground
133 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x35 mm²
26,8 mm
0,524 Ω/km
1523,4 kg/km
A
Current Carrying Capacity in Air
129 A
Current Carrying Capacity in Ground
159 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x10 mm²
20,5 mm
1,83 Ω/km
832,58 kg/km
A
Current Carrying Capacity in Air
59 A
Current Carrying Capacity in Ground
79 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x16 mm²
22,6 mm
1,15 Ω/km
1078,5 kg/km
A
Current Carrying Capacity in Air
79 A
Current Carrying Capacity in Ground
102 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x16+10 mm²
23,18 mm
1,15 / 1,83 Ω/km
1552,6 kg/km
A
Current Carrying Capacity in Air
79 A
Current Carrying Capacity in Ground
102 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x25 mm²
26,4 mm
0,727 Ω/km
1512,6 kg/km
A
Current Carrying Capacity in Air
106 A
Current Carrying Capacity in Ground
133 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x25+16 mm²
26,99 mm
0,727 / 1,15 Ω/km
2110,6 kg/km
A
Current Carrying Capacity in Air
106 A
Current Carrying Capacity in Ground
133 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x35 mm²
28,5 mm
0,524 Ω/km
1873,1 kg/km
A
Current Carrying Capacity in Air
129 A
Current Carrying Capacity in Ground
159 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x35+16 mm²
28,74 mm
0,524 / 1,15 Ω/km
2480,9 kg/km
A
Current Carrying Capacity in Air
129 A
Current Carrying Capacity in Ground
159 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x50 mm²
32,3 mm
0,387 Ω/km
2421,3 kg/km
A
Current Carrying Capacity in Air
157 A
Current Carrying Capacity in Ground
188 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x50+25 mm²
33 mm
0,387 / 0,727 Ω/km
3213,1 kg/km
A
Current Carrying Capacity in Air
157 A
Current Carrying Capacity in Ground
188 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x70 mm²
36,2 mm
0,268 Ω/km
3227,4 kg/km
A
Current Carrying Capacity in Air
199 A
Current Carrying Capacity in Ground
232 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x70+35 mm²
37,47 mm
0,268 / 0,524 Ω/km
4420,6 kg/km
A
Current Carrying Capacity in Air
199 A
Current Carrying Capacity in Ground
232 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x95 mm²
42,4 mm
0,193 Ω/km
4842,7 kg/km
A
Current Carrying Capacity in Air
246 A
Current Carrying Capacity in Ground
280 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x95+50 mm²
42,71 mm
0,193 / 0,387 Ω/km
5739 kg/km
A
Current Carrying Capacity in Air
246 A
Current Carrying Capacity in Ground
280 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x120 mm²
45,3 mm
0,153 Ω/km
5741,5 kg/km
A
Current Carrying Capacity in Air
285 A
Current Carrying Capacity in Ground
318 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x120+70 mm²
46,09 mm
0,153 / 0,268 Ω/km
6904,2 kg/km
A
Current Carrying Capacity in Air
285 A
Current Carrying Capacity in Ground
318 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x150 mm²
49,8 mm
0,124 Ω/km
6906,4 kg/km
A
Current Carrying Capacity in Air
326 A
Current Carrying Capacity in Ground
359 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x150+70 mm²
49,91 mm
0,124 / 0,268 Ω/km
8039,5 kg/km
A
Current Carrying Capacity in Air
326 A
Current Carrying Capacity in Ground
359 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x185 mm²
54,8 mm
0,0991 Ω/km
8411 kg/km
A
Current Carrying Capacity in Air
374 A
Current Carrying Capacity in Ground
406 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x185+95 mm²
55,81 mm
0,0991 / 0,193 Ω/km
10192,6 kg/km
A
Current Carrying Capacity in Air
374 A
Current Carrying Capacity in Ground
406 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x240 mm²
61,7 mm
0,0754 Ω/km
10731 kg/km
A
Current Carrying Capacity in Air
445 A
Current Carrying Capacity in Ground
473 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x240+120 mm²
62,03 mm
0,754 / 0,153 Ω/km
12718,9 kg/km
A
Current Carrying Capacity in Air
445 A
Current Carrying Capacity in Ground
473 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x10 mm²
22 mm
1,83 Ω/km
976,86 kg/km
A
Current Carrying Capacity in Air
60 A
Current Carrying Capacity in Ground
75 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x16 mm²
24,4 mm
1,15 Ω/km
1287 kg/km
A
Current Carrying Capacity in Air
80 A
Current Carrying Capacity in Ground
98 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x25 mm²
28,8 mm
0,727 Ω/km
1833,7 kg/km
A
Current Carrying Capacity in Air
106 A
Current Carrying Capacity in Ground
128 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x35 mm²
31,2 mm
0,524 Ω/km
2295,4 kg/km
A
Current Carrying Capacity in Air
131 A
Current Carrying Capacity in Ground
157 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x50 mm²
35,4 mm
0,387 Ω/km
2974,3 kg/km
A
Current Carrying Capacity in Air
159 A
Current Carrying Capacity in Ground
185 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x70 mm²
41 mm
0,268 Ω/km
4534,1 kg/km
A
Current Carrying Capacity in Air
202 A
Current Carrying Capacity in Ground
228 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x95 mm²
46,6 mm
0,193 Ω/km
5956,1 kg/km
A
Current Carrying Capacity in Air
244 A
Current Carrying Capacity in Ground
275 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x120 mm²
49,8 mm
0,153 Ω/km
7094,9 kg/km
A
Current Carrying Capacity in Air
282 A
Current Carrying Capacity in Ground
313 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x150 mm²
54,9 mm
0,124 Ω/km
8566,6 kg/km
A
Current Carrying Capacity in Air
324 A
Current Carrying Capacity in Ground
353 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x185 mm²
61 mm
0,0991 Ω/km
10548,3 kg/km
A
Current Carrying Capacity in Air
371 A
Current Carrying Capacity in Ground
399 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x240 mm²
68,1 mm
0,0754 Ω/km
13382 kg/km
A
Current Carrying Capacity in Air
436 A
Current Carrying Capacity in Ground
464 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x10 mm²
23,6 mm
1,83 Ω/km
1124,2 kg/km
A
Current Carrying Capacity in Air
60 A
Current Carrying Capacity in Ground
75 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x16 mm²
26,3 mm
1,15 Ω/km
1498,3 kg/km
A
Current Carrying Capacity in Air
80 A
Current Carrying Capacity in Ground
98 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x25 mm²
31,3 mm
0,727 Ω/km
2159,3 kg/km
A
Current Carrying Capacity in Air
106 A
Current Carrying Capacity in Ground
128 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x35 mm²
34 mm
0,524 Ω/km
2721,6 kg/km
A
Current Carrying Capacity in Air
131 A
Current Carrying Capacity in Ground
157 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x50 mm²
40,1 mm
0,387 Ω/km
4081,4 kg/km
A
Current Carrying Capacity in Air
159 A
Current Carrying Capacity in Ground
185 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x70 mm²
44,9 mm
0,268 Ω/km
5386,8 kg/km
A
Current Carrying Capacity in Air
202 A
Current Carrying Capacity in Ground
228 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x95 mm²
51,1 mm
0,193 Ω/km
7100,9 kg/km
A
Current Carrying Capacity in Air
244 A
Current Carrying Capacity in Ground
275 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x120 mm²
54,7 mm
0,153 Ω/km
8493,8 kg/km
A
Current Carrying Capacity in Air
282 A
Current Carrying Capacity in Ground
313 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x150 mm²
60,8 mm
0,124 Ω/km
10341,1 kg/km
A
Current Carrying Capacity in Air
324 A
Current Carrying Capacity in Ground
353 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x185 mm²
67 mm
0,0991 Ω/km
12648 kg/km
A
Current Carrying Capacity in Air
371 A
Current Carrying Capacity in Ground
399 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x240 mm²
75,1 mm
0,0754 Ω/km
16125,2 kg/km
A
Current Carrying Capacity in Air
436 A
Current Carrying Capacity in Ground
464 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Layer Structure
Double Steel Tape
Armour
Double Steel Tape
Minimum Bending Radius
15 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1