U-1000 R2V
XLPE Insulated Power Cables
Suitable for use in indoor and industrial factory settings or distribution centers where mechanical damage is not expected, in facilities experiencing sudden load changes, and at high operating temperatures. Resistant to short-term sudden temperature increases. Has higher electrical insulation than PVC. These cables are designed with special color coding on their outer sheath for easy identification of 1.5-2.5-4-6-10-16 mm² sections without measuring. They can be used in all weather conditions without any additional protection.


Twisted
Technical Specifications
Product
Current Carrying Capacity in Air
77 A
Current Carrying Capacity in Ground
89 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
380 A
Current Carrying Capacity in Ground
349 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
437 A
Current Carrying Capacity in Ground
393 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
102 A
Current Carrying Capacity in Ground
115 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
507 A
Current Carrying Capacity in Ground
445 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
604 A
Current Carrying Capacity in Ground
517 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
138 A
Current Carrying Capacity in Ground
148 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
697 A
Current Carrying Capacity in Ground
663 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
170 A
Current Carrying Capacity in Ground
177 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
207 A
Current Carrying Capacity in Ground
209 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
263 A
Current Carrying Capacity in Ground
256 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
325 A
Current Carrying Capacity in Ground
307 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
24 A
Current Carrying Capacity in Ground
31 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
74 A
Current Carrying Capacity in Ground
86 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
98 A
Current Carrying Capacity in Ground
112 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
32 A
Current Carrying Capacity in Ground
40 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
133 A
Current Carrying Capacity in Ground
145 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
162 A
Current Carrying Capacity in Ground
174 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
42 A
Current Carrying Capacity in Ground
52 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
53 A
Current Carrying Capacity in Ground
64 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
24 A
Current Carrying Capacity in Ground
31 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
74 A
Current Carrying Capacity in Ground
86 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
359 A
Current Carrying Capacity in Ground
348 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
359 A
Current Carrying Capacity in Ground
348 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
412 A
Current Carrying Capacity in Ground
392 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
412 A
Current Carrying Capacity in Ground
392 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
98 A
Current Carrying Capacity in Ground
112 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
98 A
Current Carrying Capacity in Ground
112 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
475 A
Current Carrying Capacity in Ground
444 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
475 A
Current Carrying Capacity in Ground
444 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
32 A
Current Carrying Capacity in Ground
40 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
564 A
Current Carrying Capacity in Ground
517 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
564 A
Current Carrying Capacity in Ground
517 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
133 A
Current Carrying Capacity in Ground
145 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
133 A
Current Carrying Capacity in Ground
145 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
649 A
Current Carrying Capacity in Ground
585 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
162 A
Current Carrying Capacity in Ground
174 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
162 A
Current Carrying Capacity in Ground
174 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
42 A
Current Carrying Capacity in Ground
52 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
197 A
Current Carrying Capacity in Ground
206 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
197 A
Current Carrying Capacity in Ground
206 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
53 A
Current Carrying Capacity in Ground
64 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
250 A
Current Carrying Capacity in Ground
254 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
250 A
Current Carrying Capacity in Ground
254 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
308 A
Current Carrying Capacity in Ground
305 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
308 A
Current Carrying Capacity in Ground
305 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
24 A
Current Carrying Capacity in Ground
31 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
74 A
Current Carrying Capacity in Ground
86 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
359 A
Current Carrying Capacity in Ground
348 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
412 A
Current Carrying Capacity in Ground
392 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
98 A
Current Carrying Capacity in Ground
112 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
475 A
Current Carrying Capacity in Ground
444 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
32 A
Current Carrying Capacity in Ground
40 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
564 A
Current Carrying Capacity in Ground
517 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
133 A
Current Carrying Capacity in Ground
145 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
649 A
Current Carrying Capacity in Ground
585 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
162 A
Current Carrying Capacity in Ground
174 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
42 A
Current Carrying Capacity in Ground
52 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
197 A
Current Carrying Capacity in Ground
206 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
53 A
Current Carrying Capacity in Ground
64 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
250 A
Current Carrying Capacity in Ground
254 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
308 A
Current Carrying Capacity in Ground
305 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
24 A
Current Carrying Capacity in Ground
31 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
74 A
Current Carrying Capacity in Ground
86 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
359 A
Current Carrying Capacity in Ground
348 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
412 A
Current Carrying Capacity in Ground
392 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
98 A
Current Carrying Capacity in Ground
112 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
475 A
Current Carrying Capacity in Ground
444 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
32 A
Current Carrying Capacity in Ground
40 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
564 A
Current Carrying Capacity in Ground
517 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
133 A
Current Carrying Capacity in Ground
145 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
162 A
Current Carrying Capacity in Ground
174 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
42 A
Current Carrying Capacity in Ground
52 A
Conductor Structure
Solid Copper (Class 1)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
197 A
Current Carrying Capacity in Ground
206 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
53 A
Current Carrying Capacity in Ground
64 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
250 A
Current Carrying Capacity in Ground
254 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
308 A
Current Carrying Capacity in Ground
305 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
XP C 32-321
Flame Retardant Test
IEC 60332-1