NYM / NVV
PVC Insulated Multi Core Installation Cables
Used in areas without mechanical stresses, in moist places, indoors, and in factories, workshops, and all types of workplaces, either under plaster or on plaster.


Twisted

Solid
Technical Specifications
Product
Current Carrying Capacity in Air
22 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
65 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
90 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
30 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
40 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
51 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
22 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
65 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
90 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
30 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
40 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
51 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
22 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
65 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
90 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
30 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
40 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
51 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
17.5 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
57 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
76 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
24 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
32 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
41 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
HD 21.4.S2;VDE 0250-204
Flame Retardant Test
IEC 60332-1