NHXMH

Halogen Free Multi Core Installation Cables
Used in hospitals, schools, hotels, shopping centers, data centers, public transport facilities, tunnels, and power plants.

Halogen Free
Twisted
Solid
Technical Specifications
Product
2x1,5 mm²
7.7 mm
12.1 Ω/km
89.87 kg/km
A
Current Carrying Capacity in Air
22 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
2x10 mm²
14.1 mm
1.83 Ω/km
380.71 kg/km
A
Current Carrying Capacity in Air
70 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
2x16 mm²
16.7 mm
1.15 Ω/km
558.89 kg/km
A
Current Carrying Capacity in Air
80 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
2x2,5 mm²
8.5 mm
7.41 Ω/km
117.79 kg/km
A
Current Carrying Capacity in Air
30 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
2x4 mm²
10.6 mm
4.61 Ω/km
191.61 kg/km
A
Current Carrying Capacity in Air
40 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
2x6 mm²
11.5 mm
3.08 Ω/km
244.29 kg/km
A
Current Carrying Capacity in Air
51 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
3x1,5 mm²
8.08 mm
12.1 Ω/km
105.92 kg/km
A
Current Carrying Capacity in Air
22 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
3x10 mm²
14.88 mm
1.83 Ω/km
469.18 kg/km
A
Current Carrying Capacity in Air
70 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
3x16 mm²
17.68 mm
1.15 Ω/km
696.68 kg/km
A
Current Carrying Capacity in Air
80 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
3x2,5 mm²
8.94 mm
7.41 Ω/km
142.24 kg/km
A
Current Carrying Capacity in Air
30 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
3x4 mm²
11.14 mm
4.61 Ω/km
229.37 kg/km
A
Current Carrying Capacity in Air
40 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
3x6 mm²
12.52 mm
3.08 Ω/km
310.09 kg/km
A
Current Carrying Capacity in Air
51 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
4x1,5 mm²
9.29 mm
12.1 Ω/km
140.36 kg/km
A
Current Carrying Capacity in Air
22 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
4x10 mm²
16.14 mm
1.83 Ω/km
574.88 kg/km
A
Current Carrying Capacity in Air
70 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
4x16 mm²
19.28 mm
1.15 Ω/km
860.36 kg/km
A
Current Carrying Capacity in Air
80 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
4x2,5 mm²
10.4 mm
7.41 Ω/km
192.53 kg/km
A
Current Carrying Capacity in Air
30 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
4x4 mm²
12.43 mm
4.61 Ω/km
287.69 kg/km
A
Current Carrying Capacity in Air
40 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
4x6 mm²
13.52 mm
3.08 Ω/km
376.36 kg/km
A
Current Carrying Capacity in Air
51 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
5x1,5 mm²
10.15 mm
12.1 Ω/km
167.38 kg/km
A
Current Carrying Capacity in Air
22 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
5x10 mm²
17.5 mm
1.83 Ω/km
683.51 kg/km
A
Current Carrying Capacity in Air
70 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
5x16 mm²
21.81 mm
1.15 Ω/km
1072.13 kg/km
A
Current Carrying Capacity in Air
80 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
5x2,5 mm²
11.23 mm
7.41 Ω/km
225.96 kg/km
A
Current Carrying Capacity in Air
30 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
5x4 mm²
13.38 mm
4.61 Ω/km
336.94 kg/km
A
Current Carrying Capacity in Air
40 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
5x6 mm²
14.6 mm
3.08 Ω/km
444.61 kg/km
A
Current Carrying Capacity in Air
51 A
Conductor Structure
Solid or Stranded Copper (Class 1;Class 2)
Operating Voltage (AC)
300 / 500 VAC
Operating Voltage (DC)
300 / 500 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
XLPE
Filler
HFFR or Kraft Paper Tape
Sheath
HFFR
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
VDE 250-214
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2