H07Z1-K

Halogen Free Flexible Installation Cables
Used in enclosed areas that require higher safety in case of fire, such as hotels, schools, high-rise buildings, hospitals, data centers, and business centers where people are densely populated.

Halogen Free
Twisted
Technical Specifications
Product
1,5 mm²
2.95 mm
13.3 Ω/km
19.5 kg/km
A
Current Carrying Capacity in Air
24 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
10 mm²
6.1 mm
1.91 Ω/km
108.17 kg/km
A
Current Carrying Capacity in Air
73 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
120 mm²
17.1 mm
0.161 Ω/km
1105.4 kg/km
A
Current Carrying Capacity in Air
344 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
150 mm²
18.9 mm
0.129 Ω/km
1375.2 kg/km
A
Current Carrying Capacity in Air
391 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
16 mm²
7.1 mm
1.21 Ω/km
160.5 kg/km
A
Current Carrying Capacity in Air
98 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
185 mm²
21.9 mm
0.106 Ω/km
1700.8 kg/km
A
Current Carrying Capacity in Air
448 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
2,5 mm²
3.55 mm
7.98 Ω/km
30.27 kg/km
A
Current Carrying Capacity in Air
32 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
240 mm²
26.6 mm
0.0801 Ω/km
2240.2 kg/km
A
Current Carrying Capacity in Air
528 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
25 mm²
8.7 mm
0.78 Ω/km
245.42 kg/km
A
Current Carrying Capacity in Air
129 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
300 mm²
29.6 mm
0.0641 Ω/km
2796.1 kg/km
A
Current Carrying Capacity in Air
620 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
35 mm²
10 mm
0.554 Ω/km
338.39 kg/km
A
Current Carrying Capacity in Air
158 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
4 mm²
4.05 mm
4.95 Ω/km
43.98 kg/km
A
Current Carrying Capacity in Air
42 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
50 mm²
11.85 mm
0.386 Ω/km
482.52 kg/km
A
Current Carrying Capacity in Air
198 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
6 mm²
4.6 mm
3.3 Ω/km
61.92 kg/km
A
Current Carrying Capacity in Air
54 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
70 mm²
13.55 mm
0.272 Ω/km
665.33 kg/km
A
Current Carrying Capacity in Air
245 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1
95 mm²
15.6 mm
0.206 Ω/km
885.42 kg/km
A
Current Carrying Capacity in Air
292 A
Conductor Structure
Fine Stranded Copper (Class 5)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
HFFR
Current Type
AC
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-3-31
Flame Retardant Test
IEC 60332-1