H07V2-R

PVC Insulated Heat Resistant Stationary Installation Cables
Used in conditions requiring high operating temperatures (+90 °C) in household appliances, fixed installations, dry locations, distribution panels, and enclosed areas, under plaster or on plaster in factories, workshops, and all kinds of workplaces.

Twisted
Technical Specifications
Product
1,5 mm²
2.95 mm
12.1 Ω/km
20.08 kg/km
A
Current Carrying Capacity in Air
24 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
10 mm²
5.8 mm
1.83 Ω/km
106.28 kg/km
A
Current Carrying Capacity in Air
73 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
120 mm²
15.85 mm
0.153 Ω/km
1116.7 kg/km
A
Current Carrying Capacity in Air
345 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
150 mm²
17.75 mm
0.124 Ω/km
1387.8 kg/km
A
Current Carrying Capacity in Air
390 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
16 mm²
6.77 mm
1.15 Ω/km
161.29 kg/km
A
Current Carrying Capacity in Air
98 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
185 mm²
19.85 mm
0.0991 Ω/km
1743.8 kg/km
A
Current Carrying Capacity in Air
445 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
2,5 mm²
3.6 mm
7.41 Ω/km
31.8 kg/km
A
Current Carrying Capacity in Air
32 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
240 mm²
22.55 mm
0.0754 Ω/km
2291.9 kg/km
A
Current Carrying Capacity in Air
525 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
25 mm²
8.47 mm
0.727 Ω/km
252.38 kg/km
A
Current Carrying Capacity in Air
129 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
300 mm²
25.05 mm
0.0601 Ω/km
2846.3 kg/km
A
Current Carrying Capacity in Air
605 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
35 mm²
9.35 mm
0.524 Ω/km
340.17 kg/km
A
Current Carrying Capacity in Air
158 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
4 mm²
4.1 mm
4.61 Ω/km
46.12 kg/km
A
Current Carrying Capacity in Air
42 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
50 mm²
10.95 mm
0.387 Ω/km
457.7 kg/km
A
Current Carrying Capacity in Air
197 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
6 mm²
4.65 mm
3.08 Ω/km
64.59 kg/km
A
Current Carrying Capacity in Air
54 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
70 mm²
12.55 mm
0.268 Ω/km
655.73 kg/km
A
Current Carrying Capacity in Air
245 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1
95 mm²
14.65 mm
0.193 Ω/km
902.09 kg/km
A
Current Carrying Capacity in Air
290 A
Conductor Structure
Stranded Copper (Class 2)
Operating Voltage (AC)
450 / 750 VAC
Operating Voltage (DC)
450 / 750 VDC
Test Voltage (AC)
2000 - 2500 VAC
Insulation
High Temperature Resistant PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS EN 50525-2-31
Flame Retardant Test
IEC 60332-1