YAXV / NA2XY

XLPE Insulated Aluminium Power Cables
Resistant to short-term sudden temperature increases. It has higher electrical insulation compared to PVC. Used in facilities with sudden load changes, in high working temperatures within buildings, and industrial factories or distribution centers where mechanical damage is not expected.

Halogen Free
Twisted
Technical Specifications
Product
1x120 mm²
18.2 mm
0.253 Ω/km
482.92 kg/km
A
Current Carrying Capacity in Air
295 A
Current Carrying Capacity in Ground
272 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x150 mm²
22.2 mm
0.206 Ω/km
592.02 kg/km
A
Current Carrying Capacity in Air
339 A
Current Carrying Capacity in Ground
305 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x16 mm²
8.9 mm
1.91 Ω/km
102.63 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x185 mm²
22.4 mm
0.164 Ω/km
723.89 kg/km
A
Current Carrying Capacity in Air
395 A
Current Carrying Capacity in Ground
347 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x240 mm²
25.2 mm
0.125 Ω/km
924.5 kg/km
A
Current Carrying Capacity in Air
472 A
Current Carrying Capacity in Ground
404 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x25 mm²
10.5 mm
1.2 Ω/km
143.58 kg/km
A
Current Carrying Capacity in Air
106 A
Current Carrying Capacity in Ground
114 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x300 mm²
28 mm
0.1 Ω/km
1149.5 kg/km
A
Current Carrying Capacity in Air
547 A
Current Carrying Capacity in Ground
457 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x35 mm²
11.5 mm
0.868 Ω/km
176.36 kg/km
A
Current Carrying Capacity in Air
130 A
Current Carrying Capacity in Ground
136 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x400 mm²
31.2 mm
0.0778 Ω/km
1446.5 kg/km
A
Current Carrying Capacity in Air
643 A
Current Carrying Capacity in Ground
525 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x50 mm²
12.9 mm
0.641 Ω/km
223.75 kg/km
A
Current Carrying Capacity in Air
161 A
Current Carrying Capacity in Ground
162 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x70 mm²
14.7 mm
0.443 Ω/km
298.88 kg/km
A
Current Carrying Capacity in Air
204 A
Current Carrying Capacity in Ground
199 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x95 mm²
16.6 mm
0.32 Ω/km
395.49 kg/km
A
Current Carrying Capacity in Air
252 A
Current Carrying Capacity in Ground
238 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x16 mm²
17 mm
1.91 Ω/km
375.72 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x25 mm²
21 mm
1.2 Ω/km
576.03 kg/km
A
Current Carrying Capacity in Air
115 A
Current Carrying Capacity in Ground
110 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x35 mm²
23 mm
0.868 Ω/km
699.89 kg/km
A
Current Carrying Capacity in Air
140 A
Current Carrying Capacity in Ground
130 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x50 mm²
25.8 mm
0.641 Ω/km
885.26 kg/km
A
Current Carrying Capacity in Air
175 A
Current Carrying Capacity in Ground
155 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x70 mm²
29.6 mm
0.443 Ω/km
1181.29 kg/km
A
Current Carrying Capacity in Air
220 A
Current Carrying Capacity in Ground
195 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x95 mm²
33.7 mm
0.32 Ω/km
1559.75 kg/km
A
Current Carrying Capacity in Air
270 A
Current Carrying Capacity in Ground
235 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x120 mm²
39 mm
0.253 Ω/km
2137.4 kg/km
A
Current Carrying Capacity in Air
270 A
Current Carrying Capacity in Ground
266 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x120+70 mm²
41.2 mm
0,253 / 0,443 Ω/km
2345.2 kg/km
A
Current Carrying Capacity in Air
273 A
Current Carrying Capacity in Ground
268 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x150 mm²
43.4 mm
0.206 Ω/km
2635.3 kg/km
A
Current Carrying Capacity in Air
308 A
Current Carrying Capacity in Ground
299 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x150+70 mm²
44.9 mm
0,206 / 0,443 Ω/km
2784.6 kg/km
A
Current Carrying Capacity in Air
311 A
Current Carrying Capacity in Ground
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x16 mm²
17.8 mm
1.91 Ω/km
413.16 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x16+10 mm²
19.8 mm
1,910 / 3,080 Ω/km
486.61 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x185 mm²
48.3 mm
0.164 Ω/km
3248.1 kg/km
A
Current Carrying Capacity in Air
357 A
Current Carrying Capacity in Ground
340 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x185+95 mm²
50.9 mm
0,164 / 0,320 Ω/km
3577.1 kg/km
A
Current Carrying Capacity in Air
360 A
Current Carrying Capacity in Ground
342 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x240 mm²
54.8 mm
0.125 Ω/km
4199.5 kg/km
A
Current Carrying Capacity in Air
435 A
Current Carrying Capacity in Ground
401 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x240+120 mm²
56.9 mm
0,125 / 0,253 Ω/km
4512 kg/km
A
Current Carrying Capacity in Air
427 A
Current Carrying Capacity in Ground
398 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x25 mm²
22.2 mm
1.2 Ω/km
587.8 kg/km
A
Current Carrying Capacity in Air
100 A
Current Carrying Capacity in Ground
111 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x25+16 mm²
23.3 mm
1,200 / 1,910 Ω/km
685.57 kg/km
A
Current Carrying Capacity in Air
102 A
Current Carrying Capacity in Ground
112 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x300 mm²
60.6 mm
0.1 Ω/km
5171 kg/km
A
Current Carrying Capacity in Air
501 A
Current Carrying Capacity in Ground
455 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x300x150 mm²
63 mm
0,100 / 0,206 Ω/km
5570.4 kg/km
A
Current Carrying Capacity in Air
507 A
Current Carrying Capacity in Ground
457 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x35 mm²
23.8 mm
0.868 Ω/km
752.99 kg/km
A
Current Carrying Capacity in Air
122 A
Current Carrying Capacity in Ground
132 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x35+16 mm²
25.1 mm
0,868 / 1,910 Ω/km
809.95 kg/km
A
Current Carrying Capacity in Air
126 A
Current Carrying Capacity in Ground
135 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x50 mm²
26.8 mm
0.641 Ω/km
959.76 kg/km
A
Current Carrying Capacity in Air
147 A
Current Carrying Capacity in Ground
157 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x50+25 mm²
28.8 mm
0,641 / 1,200 Ω/km
1074.9 kg/km
A
Current Carrying Capacity in Air
149 A
Current Carrying Capacity in Ground
158 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x70 mm²
31.5 mm
0.443 Ω/km
1346.5 kg/km
A
Current Carrying Capacity in Air
189 A
Current Carrying Capacity in Ground
195 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x70+35 mm²
32.9 mm
0,443 / 0,868 Ω/km
1435.3 kg/km
A
Current Carrying Capacity in Air
191 A
Current Carrying Capacity in Ground
196 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x95 mm²
35.6 mm
0.32 Ω/km
1762.6 kg/km
A
Current Carrying Capacity in Air
232 A
Current Carrying Capacity in Ground
233 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x95+50 mm²
37.1 mm
0,320 / 0,641 Ω/km
1875.8 kg/km
A
Current Carrying Capacity in Air
234 A
Current Carrying Capacity in Ground
234 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x120 mm²
43.2 mm
Ω/km
2553 kg/km
A
Current Carrying Capacity in Air
273 A
Current Carrying Capacity in Ground
268 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x150 mm²
48.1 mm
0.206 Ω/km
3181.2 kg/km
A
Current Carrying Capacity in Air
311 A
Current Carrying Capacity in Ground
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x16 mm²
20 mm
1.91 Ω/km
514.43 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x185 mm²
53.6 mm
0.164 Ω/km
3925.2 kg/km
A
Current Carrying Capacity in Air
360 A
Current Carrying Capacity in Ground
342 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x240 mm²
60.7 mm
0.125 Ω/km
5060.8 kg/km
A
Current Carrying Capacity in Air
427 A
Current Carrying Capacity in Ground
398 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x25 mm²
24.2 mm
1.2 Ω/km
753.53 kg/km
A
Current Carrying Capacity in Air
102 A
Current Carrying Capacity in Ground
112 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x300 mm²
67.4 mm
0.1 Ω/km
6280.8 kg/km
A
Current Carrying Capacity in Air
507 A
Current Carrying Capacity in Ground
457 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x35 mm²
26.7 mm
0.868 Ω/km
932.08 kg/km
A
Current Carrying Capacity in Air
126 A
Current Carrying Capacity in Ground
135 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x50 mm²
30.2 mm
0.641 Ω/km
1195.3 kg/km
A
Current Carrying Capacity in Air
149 A
Current Carrying Capacity in Ground
158 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x70 mm²
35 mm
0.443 Ω/km
1631.3 kg/km
A
Current Carrying Capacity in Air
191 A
Current Carrying Capacity in Ground
196 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x95 mm²
39.3 mm
0.32 Ω/km
2114.1 kg/km
A
Current Carrying Capacity in Air
234 A
Current Carrying Capacity in Ground
234 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x120 mm²
48.7 mm
0.253 Ω/km
3145.7 kg/km
A
Current Carrying Capacity in Air
273 A
Current Carrying Capacity in Ground
268 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x150 mm²
54.5 mm
0.206 Ω/km
3914.2 kg/km
A
Current Carrying Capacity in Air
311 A
Current Carrying Capacity in Ground
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x16 mm²
22.1 mm
1.91 Ω/km
608.23 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x185 mm²
60.6 mm
0.164 Ω/km
4805 kg/km
A
Current Carrying Capacity in Air
360 A
Current Carrying Capacity in Ground
342 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x240 mm²
68.1 mm
0.125 Ω/km
6097.4 kg/km
A
Current Carrying Capacity in Air
427 A
Current Carrying Capacity in Ground
398 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x25 mm²
26.4 mm
1.2 Ω/km
864.3 kg/km
A
Current Carrying Capacity in Air
102 A
Current Carrying Capacity in Ground
112 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x300 mm²
75.2 mm
0.1 Ω/km
7489.6 kg/km
A
Current Carrying Capacity in Air
507 A
Current Carrying Capacity in Ground
457 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x35 mm²
29.3 mm
0.868 Ω/km
1079.9 kg/km
A
Current Carrying Capacity in Air
126 A
Current Carrying Capacity in Ground
135 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x50 mm²
33.8 mm
0.641 Ω/km
1439.1 kg/km
A
Current Carrying Capacity in Air
149 A
Current Carrying Capacity in Ground
158 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x70 mm²
38.9 mm
0.443 Ω/km
1936 kg/km
A
Current Carrying Capacity in Air
191 A
Current Carrying Capacity in Ground
196 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x95 mm²
44.3 mm
0.32 Ω/km
2578.3 kg/km
A
Current Carrying Capacity in Air
234 A
Current Carrying Capacity in Ground
234 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Filler
PVC
Sheath
PVC
Current Type
AC & DC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
Title Type Language
YAXV / NA2XY Ürün Ana Görseli PNG
YAXV / NA2XY Ürün Kataloğu PDF
YAXV / NA2XY Ürün Kataloğu PDF
YAXV / NA2XY Ürün Kesit Görseli JPG
YAXV / NA2XY CE Kalite Sertifikası PDF
YAXV / NA2XY DOP Kalite Sertifikası PDF
YAXV / NA2XY SII Kalite Sertifikası PDF