YAVV / NAYY

PVC Insulated Aluminium Power Cables
Used as a fixed installation cable in damp places without mechanical stress, under and over plaster, inside cable ducts, wherever transmission reliability and electromagnetic protection are needed.

Twisted
Technical Specifications
Product
1x16 mm²
8,9 mm
1,91 Ω/km
109,29 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x25 mm²
10,5 mm
1,2 Ω/km
154,38 kg/km
A
Current Carrying Capacity in Air
87 A
Current Carrying Capacity in Ground
106 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x35 mm²
11,5 mm
0,868 Ω/km
188,71 kg/km
A
Current Carrying Capacity in Air
107 A
Current Carrying Capacity in Ground
127 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x50 mm²
13,2 mm
0,641 Ω/km
248,2 kg/km
A
Current Carrying Capacity in Air
131 A
Current Carrying Capacity in Ground
151 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x70 mm²
15 mm
0,443 Ω/km
330,22 kg/km
A
Current Carrying Capacity in Air
166 A
Current Carrying Capacity in Ground
185 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x95 mm²
17,1 mm
0,32 Ω/km
439,38 kg/km
A
Current Carrying Capacity in Air
205 A
Current Carrying Capacity in Ground
222 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x120 mm²
18,9 mm
0,253 Ω/km
541,86 kg/km
A
Current Carrying Capacity in Air
239 A
Current Carrying Capacity in Ground
253 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x150 mm²
20,6 mm
0,206 Ω/km
648,6 kg/km
A
Current Carrying Capacity in Air
273 A
Current Carrying Capacity in Ground
284 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x185 mm²
22,8 mm
0,164 Ω/km
793,32 kg/km
A
Current Carrying Capacity in Air
317 A
Current Carrying Capacity in Ground
322 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x240 mm²
25,8 mm
0,125 Ω/km
1023,2 kg/km
A
Current Carrying Capacity in Air
378 A
Current Carrying Capacity in Ground
375 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x300 mm²
28,3 mm
0,1 Ω/km
1242,8 kg/km
A
Current Carrying Capacity in Air
437 A
Current Carrying Capacity in Ground
425 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x400 mm²
31,7 mm
0,078 Ω/km
1575,6 kg/km
A
Current Carrying Capacity in Air
513 A
Current Carrying Capacity in Ground
487 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
1x500 mm²
36,7 mm
0,061 Ω/km
2090 kg/km
A
Current Carrying Capacity in Air
600 A
Current Carrying Capacity in Ground
558 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x16 mm²
17,8 mm
1,91 Ω/km
425,94 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x25 mm²
21,6 mm
1,2 Ω/km
631,97 kg/km
A
Current Carrying Capacity in Air
82 A
Current Carrying Capacity in Ground
102 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x35 mm²
23,6 mm
0,868 Ω/km
762,27 kg/km
A
Current Carrying Capacity in Air
100 A
Current Carrying Capacity in Ground
123 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x50 mm²
26,9 mm
0,641 Ω/km
992,93 kg/km
A
Current Carrying Capacity in Air
119 A
Current Carrying Capacity in Ground
144 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x70 mm²
30,7 mm
0,443 Ω/km
1309,4 kg/km
A
Current Carrying Capacity in Air
152 A
Current Carrying Capacity in Ground
179 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x95 mm²
35 mm
0,32 Ω/km
1722 kg/km
A
Current Carrying Capacity in Air
186 A
Current Carrying Capacity in Ground
215 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x120 mm²
38,5 mm
0,253 Ω/km
2099,9 kg/km
A
Current Carrying Capacity in Air
216 A
Current Carrying Capacity in Ground
245 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x150 mm²
41,9 mm
0,206 Ω/km
2497,4 kg/km
A
Current Carrying Capacity in Air
246 A
Current Carrying Capacity in Ground
275 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
2x185 mm²
46 mm
0,164 Ω/km
3008,6 kg/km
A
Current Carrying Capacity in Air
285 A
Current Carrying Capacity in Ground
313 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x16 mm²
18,9 mm
1,91 Ω/km
485,12 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x16+10 mm²
21,1 mm
1,91 / 3,08 Ω/km
581,83 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x25 mm²
22,3 mm
1,2 Ω/km
682 kg/km
A
Current Carrying Capacity in Air
82 A
Current Carrying Capacity in Ground
102 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x25+16 mm²
23,1 mm
1,20 / 1,91 Ω/km
743,94 kg/km
A
Current Carrying Capacity in Air
82 A
Current Carrying Capacity in Ground
102 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x35 mm²
25,1 mm
0,868 Ω/km
872,7 kg/km
A
Current Carrying Capacity in Air
100 A
Current Carrying Capacity in Ground
123 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x35+16 mm²
25,1 mm
0,868 / 1,91 Ω/km
904,89 kg/km
A
Current Carrying Capacity in Air
100 A
Current Carrying Capacity in Ground
123 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x50 mm²
28,9 mm
0,641 Ω/km
1156,2 kg/km
A
Current Carrying Capacity in Air
119 A
Current Carrying Capacity in Ground
144 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x50+25 mm²
29,3 mm
0,641 / 1,20 Ω/km
1209,3 kg/km
A
Current Carrying Capacity in Air
119 A
Current Carrying Capacity in Ground
144 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x70 mm²
32,8 mm
0,443 Ω/km
1514,9 kg/km
A
Current Carrying Capacity in Air
152 A
Current Carrying Capacity in Ground
179 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x70+35 mm²
33,1 mm
0,443 / 0,868 Ω/km
1533,4 kg/km
A
Current Carrying Capacity in Air
152 A
Current Carrying Capacity in Ground
179 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x95 mm²
37,5 mm
0,32 Ω/km
2008,7 kg/km
A
Current Carrying Capacity in Air
186 A
Current Carrying Capacity in Ground
215 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x95+50 mm²
37,6 mm
0,320 / 0,641 Ω/km
1963,1 kg/km
A
Current Carrying Capacity in Air
186 A
Current Carrying Capacity in Ground
215 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x120 mm²
41,2 mm
0,253 Ω/km
2448,5 kg/km
A
Current Carrying Capacity in Air
216 A
Current Carrying Capacity in Ground
245 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x120+70 mm²
41,2 mm
0,253 / 0,443 Ω/km
2444,1 kg/km
A
Current Carrying Capacity in Air
216 A
Current Carrying Capacity in Ground
245 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x150 mm²
45 mm
0,206 Ω/km
2932,3 kg/km
A
Current Carrying Capacity in Air
246 A
Current Carrying Capacity in Ground
275 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x150+70 mm²
45,2 mm
0,206 / 0,443 Ω/km
2887,6 kg/km
A
Current Carrying Capacity in Air
246 A
Current Carrying Capacity in Ground
275 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x185 mm²
49,5 mm
0,164 Ω/km
3541,9 kg/km
A
Current Carrying Capacity in Air
285 A
Current Carrying Capacity in Ground
313 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x185+95 mm²
51,1 mm
0,164 / 0,320 Ω/km
3653,7 kg/km
A
Current Carrying Capacity in Air
285 A
Current Carrying Capacity in Ground
313 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x240 mm²
56,1 mm
0,125 Ω/km
4566,9 kg/km
A
Current Carrying Capacity in Air
338 A
Current Carrying Capacity in Ground
364 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x240+120 mm²
57,4 mm
0,125 / 0,253 Ω/km
4747,5 kg/km
A
Current Carrying Capacity in Air
338 A
Current Carrying Capacity in Ground
364 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x300 mm²
61,6 mm
0,1 Ω/km
5538,5 kg/km
A
Current Carrying Capacity in Air
400 A
Current Carrying Capacity in Ground
419 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x300+150 mm²
65,5 mm
0,100 / 0,206 Ω/km
6239,3 kg/km
A
Current Carrying Capacity in Air
400 A
Current Carrying Capacity in Ground
419 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
3x400+185 mm²
71,9 mm
0,0778 / 0,164 Ω/km
7600,7 kg/km
A
Current Carrying Capacity in Air
472 A
Current Carrying Capacity in Ground
484 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x16 mm²
20,3 mm
1,91 Ω/km
553,21 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x25 mm²
24,1 mm
1,2 Ω/km
793,71 kg/km
A
Current Carrying Capacity in Air
82 A
Current Carrying Capacity in Ground
102 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x35 mm²
26,4 mm
0,868 Ω/km
1013,9 kg/km
A
Current Carrying Capacity in Air
100 A
Current Carrying Capacity in Ground
123 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x50 mm²
31 mm
0,641 Ω/km
1401,6 kg/km
A
Current Carrying Capacity in Air
119 A
Current Carrying Capacity in Ground
144 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x70 mm²
35,9 mm
0,443 Ω/km
1787,8 kg/km
A
Current Carrying Capacity in Air
152 A
Current Carrying Capacity in Ground
179 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x95 mm²
40,3 mm
0,32 Ω/km
2274,9 kg/km
A
Current Carrying Capacity in Air
186 A
Current Carrying Capacity in Ground
215 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x120 mm²
44,4 mm
0,253 Ω/km
2815,3 kg/km
A
Current Carrying Capacity in Air
216 A
Current Carrying Capacity in Ground
245 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x150 mm²
48,6 mm
0,206 Ω/km
3382,1 kg/km
A
Current Carrying Capacity in Air
246 A
Current Carrying Capacity in Ground
275 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x185 mm²
53,9 mm
0,164 Ω/km
4087,7 kg/km
A
Current Carrying Capacity in Air
285 A
Current Carrying Capacity in Ground
313 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x240 mm²
61,2 mm
0,125 Ω/km
5372,9 kg/km
A
Current Carrying Capacity in Air
338 A
Current Carrying Capacity in Ground
364 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x300 mm²
68,7 mm
0,1 Ω/km
6771,3 kg/km
A
Current Carrying Capacity in Air
400 A
Current Carrying Capacity in Ground
419 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
4x400 mm²
76,9 mm
0,0778 Ω/km
8545,8 kg/km
A
Current Carrying Capacity in Air
472 A
Current Carrying Capacity in Ground
484 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x16 mm²
23,1 mm
1,91 Ω/km
691,83 kg/km
A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x25 mm²
27,5 mm
1,2 Ω/km
983,9 kg/km
A
Current Carrying Capacity in Air
82 A
Current Carrying Capacity in Ground
102 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x35 mm²
30,8 mm
0,868 Ω/km
1246,6 kg/km
A
Current Carrying Capacity in Air
100 A
Current Carrying Capacity in Ground
123 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x50 mm²
35,6 mm
0,641 Ω/km
1657,6 kg/km
A
Current Carrying Capacity in Air
119 A
Current Carrying Capacity in Ground
144 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x70 mm²
40,6 mm
0,443 Ω/km
2191,5 kg/km
A
Current Carrying Capacity in Air
152 A
Current Carrying Capacity in Ground
179 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x95 mm²
46,4 mm
0,32 Ω/km
2904 kg/km
A
Current Carrying Capacity in Air
186 A
Current Carrying Capacity in Ground
215 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x120 mm²
51,1 mm
0,253 Ω/km
3554,2 kg/km
A
Current Carrying Capacity in Air
216 A
Current Carrying Capacity in Ground
245 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x150 mm²
55,8 mm
0,206 Ω/km
4254,8 kg/km
A
Current Carrying Capacity in Air
246 A
Current Carrying Capacity in Ground
275 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x185 mm²
61,3 mm
0,164 Ω/km
5119,9 kg/km
A
Current Carrying Capacity in Air
285 A
Current Carrying Capacity in Ground
313 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x240 mm²
69,7 mm
0,125 Ω/km
6635,3 kg/km
A
Current Carrying Capacity in Air
338 A
Current Carrying Capacity in Ground
364 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
5x300 mm²
76,6 mm
0,1 Ω/km
8055,8 kg/km
A
Current Carrying Capacity in Air
400 A
Current Carrying Capacity in Ground
419 A
Conductor Structure
Stranded Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
PVC
Filler
PE
Sheath
PVC
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
70 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
160 °C
Standard
TS IEC 60502-1
Flame Retardant Test
IEC 60332-1
Title Type Language
YAVV / NAYY Ürün Ana Görseli PNG
YAVV / NAYY Ürün Kataloğu PDF
YAVV / NAYY Ürün Kesit Görseli JPG
YAVV / NAYY CE Kalite Sertifikası PDF
YAVV / NAYY DOP Kalite Sertifikası PDF
YAVV / NAYY TSE Kalite Sertifikası PDF
YAVV / NAYY VDE Kalite Sertifikası PDF
How can we help you?