NA2XH (SM)
XLPE Insulated Aluminium Power Cables
Used in hospitals, schools, hotels, shopping centers, data centers, public transport facilities, tunnels, and power plants.
.png)

Halogen Free

Twisted
Technical Specifications
Product
Current Carrying Capacity in Air
273 A
Current Carrying Capacity in Ground
268 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
311 A
Current Carrying Capacity in Ground
300 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
360 A
Current Carrying Capacity in Ground
342 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
427 A
Current Carrying Capacity in Ground
398 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
507 A
Current Carrying Capacity in Ground
457 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
149 A
Current Carrying Capacity in Ground
158 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
191 A
Current Carrying Capacity in Ground
196 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
234 A
Current Carrying Capacity in Ground
234 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
273 A
Current Carrying Capacity in Ground
268 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
311 A
Current Carrying Capacity in Ground
300 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
360 A
Current Carrying Capacity in Ground
342 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
427 A
Current Carrying Capacity in Ground
398 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
507 A
Current Carrying Capacity in Ground
457 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
149 A
Current Carrying Capacity in Ground
158 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
191 A
Current Carrying Capacity in Ground
196 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2
Current Carrying Capacity in Air
234 A
Current Carrying Capacity in Ground
234 A
Conductor Structure
Sector Conducted Aluminum (Class 2)
Operating Voltage (AC)
600 / 1000 VAC
Operating Voltage (DC)
600 / 1000 VDC
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Sheath
HFFR
Current Type
AC
Layer Structure
PP Tape
Tape
Polypropylene
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
TS HD 604 S1
Flame Retardant Test
IEC 60332-1
Flame Propagation Test
EN 60332-3-24
Smoke Density Test
EN 61034-2
Halogen Free Test
EN 60754-2