ACSR (CSA)

Steel Reinforced Aluminium Conductors
Manufactured according to TS EN 50182 standards from aluminum wires and zinc-coated steel wires. Conductors are stranded concentrically in seven or more layers. If the conductor consists of multiple layers, adjacent layers are stranded in opposite directions. Production can be made according to DIN, BS, ASTM, NF, CSA, EN standards upon request. Used in medium and high voltage transmission lines.

Twisted
Technical Specifications
Product
241,68 mm²
21.2 mm
0.1194 Ω/km
853 kg/km
A
Current Carrying Capacity in Air
452 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,08 ad-mm
Number and Wire Diameter (Conductor)
22/3,74 ad-mm
Steel Wire Cross-Section
23,74 mm² mm²
Current Type
AC
Standard
CSA C 49
282 mm²
22.88 mm
0.1024 Ω/km
993 kg/km
A
Current Carrying Capacity in Air
496 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,24 ad-mm
Number and Wire Diameter (Conductor)
22/4,04 ad-mm
Steel Wire Cross-Section
27,68 mm² mm²
Current Type
AC
Standard
CSA C 49
306,58 mm²
23.86 mm
0.0942 Ω/km
1080 kg/km
A
Current Carrying Capacity in Air
519 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,34 ad-mm
Number and Wire Diameter (Conductor)
22/4,21 ad-mm
Steel Wire Cross-Section
30,07 mm² mm²
Current Type
AC
Standard
CSA C 49
322,26 mm²
24.48 mm
0.0896 Ω/km
1135 kg/km
A
Current Carrying Capacity in Air
532 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,40 ad-mm
Number and Wire Diameter (Conductor)
22/4,32 ad-mm
Steel Wire Cross-Section
31,61 mm² mm²
Current Type
AC
Standard
CSA C 49
337,74 mm²
24.54 mm
0.0856 Ω/km
1068 kg/km
A
Current Carrying Capacity in Air
546 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/1,78 ad-mm
Number and Wire Diameter (Conductor)
42/3,20 ad-mm
Steel Wire Cross-Section
17,35 mm² mm²
Current Type
AC
Standard
CSA C 49
362,58 mm²
25.38 mm
0.0797 Ω/km
1148 kg/km
A
Current Carrying Capacity in Air
573 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/1,84 ad-mm
Number and Wire Diameter (Conductor)
42/3,31 ad-mm
Steel Wire Cross-Section
18,65 mm² mm²
Current Type
AC
Standard
CSA C 49
402,8 mm²
26.82 mm
0.0719 Ω/km
1274 kg/km
A
Current Carrying Capacity in Air
610 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/1,94 ad-mm
Number and Wire Diameter (Conductor)
42/3,50 ad-mm
Steel Wire Cross-Section
20,71 mm² mm²
Current Type
AC
Standard
CSA C 49
443,1 mm²
28.14 mm
0.0653 Ω/km
1402 kg/km
A
Current Carrying Capacity in Air
645 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,04 ad-mm
Number and Wire Diameter (Conductor)
42/3,67 ad-mm
Steel Wire Cross-Section
22,84 mm² mm²
Current Type
AC
Standard
CSA C 49
456,1 mm²
28.53 mm
0.0633 Ω/km
1442 kg/km
A
Current Carrying Capacity in Air
655 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,07 ad-mm
Number and Wire Diameter (Conductor)
42/3,72 ad-mm
Steel Wire Cross-Section
23,42 mm² mm²
Current Type
AC
Standard
CSA C 49
483,4 mm²
29.87 mm
0.0597 Ω/km
1528 kg/km
A
Current Carrying Capacity in Air
678 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,13 ad-mm
Number and Wire Diameter (Conductor)
42/3,38 ad-mm
Steel Wire Cross-Section
24,84 mm² mm²
Current Type
AC
Standard
CSA C 49
523,7 mm²
30.57 mm
0.0551 Ω/km
1657 kg/km
A
Current Carrying Capacity in Air
710 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,21 ad-mm
Number and Wire Diameter (Conductor)
42/3,99 ad-mm
Steel Wire Cross-Section
26,97 mm² mm²
Current Type
AC
Standard
CSA C 49
563,9 mm²
31.74 mm
0.0512 Ω/km
1783 kg/km
A
Current Carrying Capacity in Air
741 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,30 ad-mm
Number and Wire Diameter (Conductor)
42/4,41 ad-mm
Steel Wire Cross-Section
28,97 mm² mm²
Current Type
AC
Standard
CSA C 49
604,3 mm²
32.82 mm
0.0479 Ω/km
1911 kg/km
A
Current Carrying Capacity in Air
772 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,38 ad-mm
Number and Wire Diameter (Conductor)
42/4,28 ad-mm
Steel Wire Cross-Section
31,1 mm² mm²
Current Type
AC
Standard
CSA C 49
644,51 mm²
33.9 mm
0.0449 Ω/km
2039 kg/km
A
Current Carrying Capacity in Air
800 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,46 ad-mm
Number and Wire Diameter (Conductor)
42/4,42 ad-mm
Steel Wire Cross-Section
33,16 mm² mm²
Current Type
AC
Standard
CSA C 49
684,84 mm²
34.95 mm
0.0423 Ω/km
2166 kg/km
A
Current Carrying Capacity in Air
829 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,53 ad-mm
Number and Wire Diameter (Conductor)
42/4,56 ad-mm
Steel Wire Cross-Section
35,23 mm² mm²
Current Type
AC
Standard
CSA C 49
725,1 mm²
35.97 mm
0.0397 Ω/km
2294 kg/km
A
Current Carrying Capacity in Air
858 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,61 ad-mm
Number and Wire Diameter (Conductor)
42/4,69 ad-mm
Steel Wire Cross-Section
37,35 mm² mm²
Current Type
AC
Standard
CSA C 49
765,35 mm²
36.93 mm
0.0377 Ω/km
2420 kg/km
A
Current Carrying Capacity in Air
885 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,67 ad-mm
Number and Wire Diameter (Conductor)
42/4,82 ad-mm
Steel Wire Cross-Section
39,35 mm² mm²
Current Type
AC
Standard
CSA C 49
805,7 mm²
37.72 mm
0.0358 Ω/km
2498 kg/km
A
Current Carrying Capacity in Air
910 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,52 ad-mm
Number and Wire Diameter (Conductor)
72/3,77 ad-mm
Steel Wire Cross-Section
34,84 mm² mm²
Current Type
AC
Standard
CSA C 49
805,7 mm²
38.58 mm
0.0358 Ω/km
2779 kg/km
A
Current Carrying Capacity in Air
929 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,60 ad-mm
Number and Wire Diameter (Conductor)
48/4,36 ad-mm
Steel Wire Cross-Section
71,1 mm² mm²
Current Type
AC
Standard
CSA C 49
Auk (102,84 mm²)
14.83 mm
0.2789 Ω/km
500 kg/km
A
Current Carrying Capacity in Air
276 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,25 ad-mm
Number and Wire Diameter (Conductor)
8/4,05 ad-mm
Steel Wire Cross-Section
92,32 mm² mm²
Current Type
AC
Actual Code (New Standard)
Auk
Standard
CSA C 49
Bantam (6,65 mm²)
5.04 mm
43218 Ω/km
87.8 kg/km
A
Current Carrying Capacity in Air
61 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
4/1,68 ad-mm
Number and Wire Diameter (Conductor)
3/1,68 ad-mm
Steel Wire Cross-Section
8,84 mm² mm²
Current Type
AC
Actual Code (New Standard)
Bantam
Standard
CSA C 49
Brahma (102,97 mm²)
18.12 mm
0.2815 Ω/km
1004.9 kg/km
A
Current Carrying Capacity in Air
287 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,48 ad-mm
Number and Wire Diameter (Conductor)
16/2,86 ad-mm
Steel Wire Cross-Section
91,87 mm² mm²
Current Type
AC
Actual Code (New Standard)
Brahma
Standard
CSA C 49
Canary (456,1 mm²)
29.52 mm
0.0633 Ω/km
1724 kg/km
A
Current Carrying Capacity in Air
660 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,28 ad-mm
Number and Wire Diameter (Conductor)
54/3,28 ad-mm
Steel Wire Cross-Section
59,1 mm² mm²
Current Type
AC
Actual Code (New Standard)
Canary
Standard
CSA C 49
Cardinal (483,4 mm²)
30.42 mm
0.0597 Ω/km
1826 kg/km
A
Current Carrying Capacity in Air
682 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,38 ad-mm
Number and Wire Diameter (Conductor)
54/3,38 ad-mm
Steel Wire Cross-Section
62,65 mm² mm²
Current Type
AC
Actual Code (New Standard)
Cardinal
Standard
CSA C 49
Chickadee (201,42 mm²)
18.85 mm
0.143 Ω/km
641 kg/km
A
Current Carrying Capacity in Air
402 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/3,77 ad-mm
Number and Wire Diameter (Conductor)
18/3,77 ad-mm
Steel Wire Cross-Section
11,16 mm² mm²
Current Type
AC
Actual Code (New Standard)
Chickadee
Standard
CSA C 49
Cochin (107,1 mm²)
16.85 mm
0.2694 Ω/km
782.8 kg/km
A
Current Carrying Capacity in Air
288 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,37 ad-mm
Number and Wire Diameter (Conductor)
12/3,37 ad-mm
Steel Wire Cross-Section
62,45 mm² mm²
Current Type
AC
Actual Code (New Standard)
Cochin
Standard
CSA C 49
Condore (402,8 mm²)
27.72 mm
0.0719 Ω/km
1521 kg/km
A
Current Carrying Capacity in Air
615 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,08 ad-mm
Number and Wire Diameter (Conductor)
54/3,08 ad-mm
Steel Wire Cross-Section
52,19 mm² mm²
Current Type
AC
Actual Code (New Standard)
Condore
Standard
CSA C 49
Crane (443,1 mm²)
29.07 mm
0.0653 Ω/km
1674 kg/km
A
Current Carrying Capacity in Air
649 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,23 ad-mm
Number and Wire Diameter (Conductor)
54/3,23 ad-mm
Steel Wire Cross-Section
57,48 mm² mm²
Current Type
AC
Actual Code (New Standard)
Crane
Standard
CSA C 49
Crow (362,58 mm²)
26.28 mm
0.0797 Ω/km
1369 kg/km
A
Current Carrying Capacity in Air
577 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,92 ad-mm
Number and Wire Diameter (Conductor)
54/2,92 ad-mm
Steel Wire Cross-Section
46,97 mm² mm²
Current Type
AC
Actual Code (New Standard)
Crow
Standard
CSA C 49
Curlew (523,7 mm²)
31.59 mm
0.0551 Ω/km
1978 kg/km
A
Current Carrying Capacity in Air
715 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,51 ad-mm
Number and Wire Diameter (Conductor)
54/3,51 ad-mm
Steel Wire Cross-Section
67,87 mm² mm²
Current Type
AC
Actual Code (New Standard)
Curlew
Standard
CSA C 49
Dorking (96,71 mm²)
16 mm
0.2982 Ω/km
706.9 kg/km
A
Current Carrying Capacity in Air
271 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,20 ad-mm
Number and Wire Diameter (Conductor)
12/3,20 ad-mm
Steel Wire Cross-Section
56,39 mm² mm²
Current Type
AC
Actual Code (New Standard)
Dorking
Standard
CSA C 49
Dotterell (89,48 mm²)
15.4 mm
0.3215 Ω/km
654.8 kg/km
A
Current Carrying Capacity in Air
260 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,08 ad-mm
Number and Wire Diameter (Conductor)
12/3,08 ad-mm
Steel Wire Cross-Section
52,19 mm² mm²
Current Type
AC
Actual Code (New Standard)
Dotterell
Standard
CSA C 49
Dove (282 mm²)
23.55 mm
0.1024 Ω/km
1137 kg/km
A
Current Carrying Capacity in Air
495 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,89 ad-mm
Number and Wire Diameter (Conductor)
26/3,72 ad-mm
Steel Wire Cross-Section
45,94 mm² mm²
Current Type
AC
Actual Code (New Standard)
Dove
Standard
CSA C 49
Drake (402,84 mm²)
28.11 mm
0.0715 Ω/km
1624 kg/km
A
Current Carrying Capacity in Air
611 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,45 ad-mm
Number and Wire Diameter (Conductor)
26/4,44 ad-mm
Steel Wire Cross-Section
65,61 mm² mm²
Current Type
AC
Actual Code (New Standard)
Drake
Standard
CSA C 49
Duck (306,58 mm²)
24.21 mm
0.0945 Ω/km
1159 kg/km
A
Current Carrying Capacity in Air
520 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,69 ad-mm
Number and Wire Diameter (Conductor)
54/2,69 ad-mm
Steel Wire Cross-Section
39,81 mm² mm²
Current Type
AC
Actual Code (New Standard)
Duck
Standard
CSA C 49
Eagle (282 mm²)
24.22 mm
0.1027 Ω/km
1293 kg/km
A
Current Carrying Capacity in Air
497 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,46 ad-mm
Number and Wire Diameter (Conductor)
30/3,46 ad-mm
Steel Wire Cross-Section
65,81 mm² mm²
Current Type
AC
Actual Code (New Standard)
Eagle
Standard
CSA C 49
Egret (322,26 mm²)
25.9 mm
0.0896 Ω/km
1467 kg/km
A
Current Carrying Capacity in Air
542 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,22 ad-mm
Number and Wire Diameter (Conductor)
30/3,70 ad-mm
Steel Wire Cross-Section
73,55 mm² mm²
Current Type
AC
Actual Code (New Standard)
Egret
Standard
CSA C 49
Falcon (805,7 mm²)
39.26 mm
0.0358 Ω/km
3028 kg/km
A
Current Carrying Capacity in Air
917 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,62 ad-mm
Number and Wire Diameter (Conductor)
54/4,36 ad-mm
Steel Wire Cross-Section
102,1 mm² mm²
Current Type
AC
Actual Code (New Standard)
Falcon
Standard
CSA C 49
Finch (563,9 mm²)
32.85 mm
0.0512 Ω/km
2121 kg/km
A
Current Carrying Capacity in Air
746 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,19 ad-mm
Number and Wire Diameter (Conductor)
54/3,65 ad-mm
Steel Wire Cross-Section
71,55 mm² mm²
Current Type
AC
Actual Code (New Standard)
Finch
Standard
CSA C 49
Goose (322,26 mm²)
24.84 mm
0.0899 Ω/km
1217 kg/km
A
Current Carrying Capacity in Air
534 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,76 ad-mm
Number and Wire Diameter (Conductor)
54/2,76 ad-mm
Steel Wire Cross-Section
41,74 mm² mm²
Current Type
AC
Actual Code (New Standard)
Goose
Standard
CSA C 49
Grackle (604,26 mm²)
33.97 mm
0.0479 Ω/km
2271 kg/km
A
Current Carrying Capacity in Air
776 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,27 ad-mm
Number and Wire Diameter (Conductor)
54/3,77 ad-mm
Steel Wire Cross-Section
76,58 mm² mm²
Current Type
AC
Actual Code (New Standard)
Grackle
Standard
CSA C 49
Grosbeak (322,26 mm²)
25.15 mm
0.0896 Ω/km
1299 kg/km
A
Current Carrying Capacity in Air
530 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,09 ad-mm
Number and Wire Diameter (Conductor)
26/3,97 ad-mm
Steel Wire Cross-Section
52,45 mm² mm²
Current Type
AC
Actual Code (New Standard)
Grosbeak
Standard
CSA C 49
Grouse (40,52 mm²)
9.32 mm
0.7077 Ω/km
221.2 kg/km
A
Current Carrying Capacity in Air
157 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/4,24 ad-mm
Number and Wire Diameter (Conductor)
8/2,54 ad-mm
Steel Wire Cross-Section
14,13 mm² mm²
Current Type
AC
Actual Code (New Standard)
Grouse
Standard
CSA C 49
Guinea (80,68 mm²)
14.6 mm
0.3579 Ω/km
587.8 kg/km
A
Current Carrying Capacity in Air
244 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,92 ad-mm
Number and Wire Diameter (Conductor)
12/2,92 ad-mm
Steel Wire Cross-Section
46,97 mm² mm²
Current Type
AC
Actual Code (New Standard)
Guinea
Standard
CSA C 49
Gull (337,74 mm²)
25.38 mm
0.0856 Ω/km
1277 kg/km
A
Current Carrying Capacity in Air
553 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,82 ad-mm
Number and Wire Diameter (Conductor)
54/2,82 ad-mm
Steel Wire Cross-Section
43,81 mm² mm²
Current Type
AC
Actual Code (New Standard)
Gull
Standard
CSA C 49
Hawk (241,68 mm²)
21.77 mm
0.1194 Ω/km
975 kg/km
A
Current Carrying Capacity in Air
450 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,67 ad-mm
Number and Wire Diameter (Conductor)
26/3,44 ad-mm
Steel Wire Cross-Section
39,42 mm² mm²
Current Type
AC
Actual Code (New Standard)
Hawk
Standard
CSA C 49
Hen (241,68 mm²)
22.4 mm
0.1198 Ω/km
1108 kg/km
A
Current Carrying Capacity in Air
453 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,20 ad-mm
Number and Wire Diameter (Conductor)
30/3,20 ad-mm
Steel Wire Cross-Section
56,39 mm² mm²
Current Type
AC
Actual Code (New Standard)
Hen
Standard
CSA C 49
Heron (253,35 mm²)
22.96 mm
0.1142 Ω/km
1162 kg/km
A
Current Carrying Capacity in Air
469 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,28 ad-mm
Number and Wire Diameter (Conductor)
30/3,28 ad-mm
Steel Wire Cross-Section
59,1 mm² mm²
Current Type
AC
Actual Code (New Standard)
Heron
Standard
CSA C 49
Ibis (201,42 mm²)
19.88 mm
0.1434 Ω/km
813 kg/km
A
Current Carrying Capacity in Air
404 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,44 ad-mm
Number and Wire Diameter (Conductor)
26/3,14 ad-mm
Steel Wire Cross-Section
32,77 mm² mm²
Current Type
AC
Actual Code (New Standard)
Ibis
Standard
CSA C 49
Lark (201,42 mm²)
20.44 mm
0.1437 Ω/km
923 kg/km
A
Current Carrying Capacity in Air
410 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,92 ad-mm
Number and Wire Diameter (Conductor)
30/2,92 ad-mm
Steel Wire Cross-Section
46,97 mm² mm²
Current Type
AC
Actual Code (New Standard)
Lark
Standard
CSA C 49
Leghorn (68,19 mm²)
13.45 mm
0.4226 Ω/km
498.5 kg/km
A
Current Carrying Capacity in Air
221 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,69 ad-mm
Number and Wire Diameter (Conductor)
12/2,69 ad-mm
Steel Wire Cross-Section
39,81 mm² mm²
Current Type
AC
Actual Code (New Standard)
Leghorn
Standard
CSA C 49
Linnet (170,45 mm²)
18.31 mm
0.1696 Ω/km
687 kg/km
A
Current Carrying Capacity in Air
368 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,25 ad-mm
Number and Wire Diameter (Conductor)
26/2,89 ad-mm
Steel Wire Cross-Section
27,81 mm² mm²
Current Type
AC
Actual Code (New Standard)
Linnet
Standard
CSA C 49
Loon (33,68 mm²)
11.34 mm
0.8514 Ω/km
445.8 kg/km
A
Current Carrying Capacity in Air
149 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
4/3,78 ad-mm
Number and Wire Diameter (Conductor)
3/3,78 ad-mm
Steel Wire Cross-Section
44,97 mm² mm²
Current Type
AC
Actual Code (New Standard)
Loon
Standard
CSA C 49
Magpie (10,58 mm²)
6.36 mm
27077 Ω/km
139.7 kg/km
A
Current Carrying Capacity in Air
77 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
4/2,12 ad-mm
Number and Wire Diameter (Conductor)
3/2,12 ad-mm
Steel Wire Cross-Section
14,13 mm² mm²
Current Type
AC
Actual Code (New Standard)
Magpie
Standard
CSA C 49
Mallard (402,8 mm²)
28.96 mm
0.0719 Ω/km
1832 kg/km
A
Current Carrying Capacity in Air
618 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,48 ad-mm
Number and Wire Diameter (Conductor)
30/4,14 ad-mm
Steel Wire Cross-Section
91,84 mm² mm²
Current Type
AC
Actual Code (New Standard)
Mallard
Standard
CSA C 49
Martin (684,84 mm²)
36.17 mm
0.0423 Ω/km
2573 kg/km
A
Current Carrying Capacity in Air
835 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,41 ad-mm
Number and Wire Diameter (Conductor)
54/4,02 ad-mm
Steel Wire Cross-Section
86,71 mm² mm²
Current Type
AC
Actual Code (New Standard)
Martin
Standard
CSA C 49
Merlin (170,45 mm²)
17.35 mm
0.1686 Ω/km
543 kg/km
A
Current Carrying Capacity in Air
364 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/3,47 ad-mm
Number and Wire Diameter (Conductor)
18/3,47 ad-mm
Steel Wire Cross-Section
9,48 mm² mm²
Current Type
AC
Actual Code (New Standard)
Merlin
Standard
CSA C 49
Minorca (56,13 mm²)
12.2 mm
0.5134 Ω/km
311.3 kg/km
A
Current Carrying Capacity in Air
198 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,44 ad-mm
Number and Wire Diameter (Conductor)
12/2,44 ad-mm
Steel Wire Cross-Section
32,77 mm² mm²
Current Type
AC
Actual Code (New Standard)
Minorca
Standard
CSA C 49
Oriole (170,45 mm²)
18.83 mm
0.1696 Ω/km
783 kg/km
A
Current Carrying Capacity in Air
370 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,69 ad-mm
Number and Wire Diameter (Conductor)
30/2,69 ad-mm
Steel Wire Cross-Section
39,81 mm² mm²
Current Type
AC
Actual Code (New Standard)
Oriole
Standard
CSA C 49
Ostrich (152 mm²)
17.28 mm
0.19 Ω/km
613 kg/km
A
Current Carrying Capacity in Air
343 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,12 ad-mm
Number and Wire Diameter (Conductor)
26/2,73 ad-mm
Steel Wire Cross-Section
24,71 mm² mm²
Current Type
AC
Actual Code (New Standard)
Ostrich
Standard
CSA C 49
Owl (135,16 mm²)
16.09 mm
0.2119 Ω/km
508 kg/km
A
Current Carrying Capacity in Air
322 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/1,74 ad-mm
Number and Wire Diameter (Conductor)
6/5,36 ad-mm
Steel Wire Cross-Section
17,55 mm² mm²
Current Type
AC
Actual Code (New Standard)
Owl
Standard
CSA C 49
Parrot (765,4 mm²)
38.25 mm
0.0377 Ω/km
2877 kg/km
A
Current Carrying Capacity in Air
890 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,55 ad-mm
Number and Wire Diameter (Conductor)
54/4,25 ad-mm
Steel Wire Cross-Section
96,84 mm² mm²
Current Type
AC
Actual Code (New Standard)
Parrot
Standard
CSA C 49
Partridge (135,16 mm²)
16.28 mm
0.2136 Ω/km
545 kg/km
A
Current Carrying Capacity in Air
321 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,00 ad-mm
Number and Wire Diameter (Conductor)
26/2,57 ad-mm
Steel Wire Cross-Section
22 mm² mm²
Current Type
AC
Actual Code (New Standard)
Partridge
Standard
CSA C 49
Pelican (241,68 mm²)
20.7 mm
0.1191 Ω/km
769 kg/km
A
Current Carrying Capacity in Air
449 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/4,14 ad-mm
Number and Wire Diameter (Conductor)
18/4,14 ad-mm
Steel Wire Cross-Section
13,42 mm² mm²
Current Type
AC
Actual Code (New Standard)
Pelican
Standard
CSA C 49
Penguin (107,23 mm²)
14.31 mm
0.2671 Ω/km
433 kg/km
A
Current Carrying Capacity in Air
276 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/4,77 ad-mm
Number and Wire Diameter (Conductor)
6/4,77 ad-mm
Steel Wire Cross-Section
17,87 mm² mm²
Current Type
AC
Actual Code (New Standard)
Penguin
Standard
CSA C 49
Petrel (51,61 mm²)
11.7 mm
0.5591 Ω/km
376.9 kg/km
A
Current Carrying Capacity in Air
193 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,34 ad-mm
Number and Wire Diameter (Conductor)
12/2,34 ad-mm
Steel Wire Cross-Section
30,01 mm² mm²
Current Type
AC
Actual Code (New Standard)
Petrel
Standard
CSA C 49
Pheasant (644,51 mm²)
35.1 mm
0.0449 Ω/km
2421 kg/km
A
Current Carrying Capacity in Air
805 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,34 ad-mm
Number and Wire Diameter (Conductor)
54/3,90 ad-mm
Steel Wire Cross-Section
81,68 mm² mm²
Current Type
AC
Actual Code (New Standard)
Pheasant
Standard
CSA C 49
Phoebe (152 mm²)
16.4 mm
0.1893 Ω/km
483 kg/km
A
Current Carrying Capacity in Air
341 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/3,28 ad-mm
Number and Wire Diameter (Conductor)
18/3,28 ad-mm
Steel Wire Cross-Section
8,45 mm² mm²
Current Type
AC
Actual Code (New Standard)
Phoebe
Standard
CSA C 49
Pigeon (85,03 mm²)
12.75 mm
0.3366 Ω/km
343 kg/km
A
Current Carrying Capacity in Air
241 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/4,25 ad-mm
Number and Wire Diameter (Conductor)
6/4,25 ad-mm
Steel Wire Cross-Section
14,19 mm² mm²
Current Type
AC
Actual Code (New Standard)
Pigeon
Standard
CSA C 49
Piper (152 mm²)
17.78 mm
0.1903 Ω/km
697 kg/km
A
Current Carrying Capacity in Air
348 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/2,54 ad-mm
Number and Wire Diameter (Conductor)
30/2,54 ad-mm
Steel Wire Cross-Section
35,48 mm² mm²
Current Type
AC
Actual Code (New Standard)
Piper
Standard
CSA C 49
Plover (725,1 mm²)
37.24 mm
0.04 Ω/km
2725 kg/km
A
Current Carrying Capacity in Air
862 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,48 ad-mm
Number and Wire Diameter (Conductor)
54/4,14 ad-mm
Steel Wire Cross-Section
91,87 mm² mm²
Current Type
AC
Actual Code (New Standard)
Plover
Standard
CSA C 49
Quail (67,42 mm²)
11.34 mm
0.4245 Ω/km
273 kg/km
A
Current Carrying Capacity in Air
211 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/3,78 ad-mm
Number and Wire Diameter (Conductor)
6/3,78 ad-mm
Steel Wire Cross-Section
11,23 mm² mm²
Current Type
AC
Actual Code (New Standard)
Quail
Standard
CSA C 49
Raven (53,48 mm²)
10.11 mm
0.5351 Ω/km
215 kg/km
A
Current Carrying Capacity in Air
186 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/3,37 ad-mm
Number and Wire Diameter (Conductor)
6/3,37 ad-mm
Steel Wire Cross-Section
8,9 mm² mm²
Current Type
AC
Actual Code (New Standard)
Raven
Standard
CSA C 49
Redwing (362,58 mm²)
27.43 mm
0.0797 Ω/km
1648 kg/km
A
Current Carrying Capacity in Air
581 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
19/2,35 ad-mm
Number and Wire Diameter (Conductor)
30/3,92 ad-mm
Steel Wire Cross-Section
82,58 mm² mm²
Current Type
AC
Actual Code (New Standard)
Redwing
Standard
CSA C 49
Robin (42,39 mm²)
9 mm
0.6752 Ω/km
171 kg/km
A
Current Carrying Capacity in Air
162 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/3,00 ad-mm
Number and Wire Diameter (Conductor)
6/3,00 ad-mm
Steel Wire Cross-Section
7,1 mm² mm²
Current Type
AC
Actual Code (New Standard)
Robin
Standard
CSA C 49
Shrike (16,84 mm²)
8.01 mm
17054 Ω/km
222.6 kg/km
A
Current Carrying Capacity in Air
99 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
4/2,67 ad-mm
Number and Wire Diameter (Conductor)
3/2,67 ad-mm
Steel Wire Cross-Section
22,45 mm² mm²
Current Type
AC
Actual Code (New Standard)
Shrike
Standard
CSA C 49
Snipe (26,17 mm²)
10.11 mm
10718 Ω/km
354.1 kg/km
A
Current Carrying Capacity in Air
132 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
4/3,37 ad-mm
Number and Wire Diameter (Conductor)
3/3,37 ad-mm
Steel Wire Cross-Section
35,68 mm² mm²
Current Type
AC
Actual Code (New Standard)
Snipe
Standard
CSA C 49
Sparrow (33,61 mm²)
8.01 mm
0.8504 Ω/km
136 kg/km
A
Current Carrying Capacity in Air
140 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/2,67 ad-mm
Number and Wire Diameter (Conductor)
6/2,67 ad-mm
Steel Wire Cross-Section
5,61 mm² mm²
Current Type
AC
Actual Code (New Standard)
Sparrow
Standard
CSA C 49
Starling (362,58 mm²)
26.68 mm
0.0797 Ω/km
1462 kg/km
A
Current Carrying Capacity in Air
575 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
7/3,28 ad-mm
Number and Wire Diameter (Conductor)
26/4,21 ad-mm
Steel Wire Cross-Section
59,03 mm² mm²
Current Type
AC
Actual Code (New Standard)
Starling
Standard
CSA C 49
Swallow (26,65 mm²)
7.14 mm
1.0738 Ω/km
108 kg/km
A
Current Carrying Capacity in Air
126 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/2,38 ad-mm
Number and Wire Diameter (Conductor)
6/2,38 ad-mm
Steel Wire Cross-Section
4,45 mm² mm²
Current Type
AC
Actual Code (New Standard)
Swallow
Standard
CSA C 49
Swan (21,16 mm²)
6.36 mm
1.3537 Ω/km
85 kg/km
A
Current Carrying Capacity in Air
109 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/2,12 ad-mm
Number and Wire Diameter (Conductor)
6/2,12 ad-mm
Steel Wire Cross-Section
3,55 mm² mm²
Current Type
AC
Actual Code (New Standard)
Swan
Standard
CSA C 49
Thrush (16,77 mm²)
5.67 mm
1.7077 Ω/km
68 kg/km
A
Current Carrying Capacity in Air
93 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/1,89 ad-mm
Number and Wire Diameter (Conductor)
6/1,89 ad-mm
Steel Wire Cross-Section
2,77 mm² mm²
Current Type
AC
Actual Code (New Standard)
Thrush
Standard
CSA C 49
Turkey (13,29 mm²)
5.04 mm
2.1535 Ω/km
54 kg/km
A
Current Carrying Capacity in Air
86 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/1,68 ad-mm
Number and Wire Diameter (Conductor)
6/1,68 ad-mm
Steel Wire Cross-Section
2,19 mm² mm²
Current Type
AC
Actual Code (New Standard)
Turkey
Standard
CSA C 49
Warbler (10,59 mm²)
4.5 mm
2.7139 Ω/km
43 kg/km
A
Current Carrying Capacity in Air
67 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/1,50 ad-mm
Number and Wire Diameter (Conductor)
6/1,50 ad-mm
Steel Wire Cross-Section
1,34 mm² mm²
Current Type
AC
Actual Code (New Standard)
Warbler
Standard
CSA C 49
Waxwing (135,16 mm²)
15.15 mm
0.2126 Ω/km
430 kg/km
A
Current Carrying Capacity in Air
319 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/3,09 ad-mm
Number and Wire Diameter (Conductor)
18/3,09 ad-mm
Steel Wire Cross-Section
7,48 mm² mm²
Current Type
AC
Actual Code (New Standard)
Waxwing
Standard
CSA C 49
Wren (8,39 mm²)
3.99 mm
3.4226 Ω/km
34 kg/km
A
Current Carrying Capacity in Air
63 A
Conductor Structure
Stranded Aluminum and Steel
Number and Wire Diameter (Steel)
1/1,33 ad-mm
Number and Wire Diameter (Conductor)
6/1,33 ad-mm
Steel Wire Cross-Section
1,42 mm² mm²
Current Type
AC
Actual Code (New Standard)
Wren
Standard
CSA C 49
Title Type Language
ACSR (CSA) Ürün Alternatif Görseli PNG
ACSR (CSA) Ürün Ana Görseli PNG
ACSR (CSA) Ürün Kataloğu PDF
ACSR (CSA) Ürün Kataloğu PDF
ACSR (CSA) Ürün Kataloğu PDF
ACSR (CSA) Ürün Kataloğu PDF
ACSR (CSA) Ürün Kataloğu PDF
ACSR (CSA) Ürün Kesit Görseli JPG
ACSR (CSA) CE Kalite Sertifikası PDF
ACSR (CSA) GOST Kalite Sertifikası PDF
ACSR (CSA) TSE Kalite Sertifikası PDF
How can we help you?
Or
Adobestock 558884015 1