ABC (NFC)
XLPE Insulated Aerial Bundled Conductor Aluminium Power Cables
More secure against short circuits and impacts compared to bare overhead conductors. This type of cable is preferred in various applications for more efficient and safe transmission of network power. These cables are particularly used in village electrification and densely populated areas where underground cabled facilities are very expensive.


Twisted
Technical Specifications
Product
Current Carrying Capacity in Air
93 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
122 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
129 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
158 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
111 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
111 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
111 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
131 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
131 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
131 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
83 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
111 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
131 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1