ABC (NFC)

XLPE Insulated Aerial Bundled Conductor Aluminium Power Cables
More secure against short circuits and impacts compared to bare overhead conductors. This type of cable is preferred in various applications for more efficient and safe transmission of network power. These cables are particularly used in village electrification and densely populated areas where underground cabled facilities are very expensive.

Twisted
Technical Specifications
Product
2x16 mm²
15 mm
1.91 Ω/km
120 kg/km
A
Current Carrying Capacity in Air
93 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
2x25 mm²
18.5 mm
1.2 Ω/km
190 kg/km
A
Current Carrying Capacity in Air
122 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
2x35 mm²
2 mm
0.868 Ω/km
250 kg/km
A
Current Carrying Capacity in Air
129 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
2x50 mm²
24 mm
0.641 Ω/km
330 kg/km
A
Current Carrying Capacity in Air
158 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x120+70 mm²
46 mm
0.253 Ω/km
1420 kg/km
A
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x120+70+16 mm²
46 mm
0.253 Ω/km
1480 kg/km
A
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x120+70+25 mm²
47 mm
0.253 Ω/km
1520 kg/km
A
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x120+70+2x16 mm²
46 mm
0.253 Ω/km
1550 kg/km
A
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x120+70+2x25 mm²
48 mm
0.253 Ω/km
1610 kg/km
A
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x120+95+25 mm²
48 mm
0.253 Ω/km
1600 kg/km
A
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x150+95 mm²
48 mm
0.206 Ω/km
1730 kg/km
A
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x150+95+16 mm²
49 mm
0.206 Ω/km
1800 kg/km
A
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x150+95+25 mm²
50 mm
0.206 Ω/km
1830 kg/km
A
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x150+95+2x16 mm²
48 mm
0.206 Ω/km
1860 kg/km
A
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x150+95+2x25 mm²
50 mm
0.206 Ω/km
1930 kg/km
A
Current Carrying Capacity in Air
344 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x25+54,6 mm²
30 mm
1.2 Ω/km
490 kg/km
A
Current Carrying Capacity in Air
111 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x25+54,6+16 mm²
30 mm
1.2 Ω/km
550 kg/km
A
Current Carrying Capacity in Air
111 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x25+54,6+2x16 mm²
30 mm
1.2 Ω/km
610 kg/km
A
Current Carrying Capacity in Air
111 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x35+54,6 mm²
33 mm
0.868 Ω/km
590 kg/km
A
Current Carrying Capacity in Air
131 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x35+54,6+16 mm²
33 mm
0.868 Ω/km
650 kg/km
A
Current Carrying Capacity in Air
131 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x35+54,6+2x16 mm²
33 mm
0.868 Ω/km
710 kg/km
A
Current Carrying Capacity in Air
131 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x50+54,6 mm²
36 mm
0.641 Ω/km
700 kg/km
A
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x50+54,6+16 mm²
36 mm
0.641 Ω/km
760 kg/km
A
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x50+54,6+25 mm²
37 mm
0.641 Ω/km
800 kg/km
A
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x50+54,6+2x16 mm²
36 mm
0.641 Ω/km
830 kg/km
A
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x50+54,6+2x25 mm²
37 mm
0.641 Ω/km
890 kg/km
A
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+54,6 mm²
38 mm
0.443 Ω/km
910 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+54,6+16 mm²
38 mm
0.443 Ω/km
970 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+54,6+25 mm²
39 mm
0.443 Ω/km
1010 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+54,6+2x16 mm²
38 mm
0.443 Ω/km
1040 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+54,6+2x25 mm²
40 mm
0.443 Ω/km
1100 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+70 mm²
41 mm
0.443 Ω/km
970 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+70+16 mm²
41 mm
0.443 Ω/km
1030 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+70+25 mm²
42 mm
0.443 Ω/km
1060 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+70+2x16 mm²
41 mm
0.443 Ω/km
1090 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x70+70+2x25 mm²
43 mm
0.443 Ω/km
1160 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+54,6 mm²
44 mm
0.32 Ω/km
1160 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+54,6+16 mm²
44 mm
0.32 Ω/km
1220 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+54,6+25 mm²
45 mm
0.32 Ω/km
1250 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+54,6+2x16 mm²
40 mm
0.32 Ω/km
1280 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+54,6+2x25 mm²
42 mm
0.32 Ω/km
1350 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+70 mm²
44 mm
0.32 Ω/km
1210 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+70+16 mm²
44 mm
0.32 Ω/km
1280 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+70+25 mm²
45 mm
0.32 Ω/km
1310 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+70+2x16 mm²
44 mm
0.32 Ω/km
1340 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
3x95+70+2x25 mm²
46 mm
0.32 Ω/km
1400 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
4x120 mm²
40 mm
0.253 Ω/km
1550 kg/km
A
Current Carrying Capacity in Air
300 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
4x16 mm²
18 mm
1.91 Ω/km
250 kg/km
A
Current Carrying Capacity in Air
83 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
4x25 mm²
22 mm
1.2 Ω/km
380 kg/km
A
Current Carrying Capacity in Air
111 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
4x35 mm²
26 mm
0.868 Ω/km
510 kg/km
A
Current Carrying Capacity in Air
131 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
4x50 mm²
28 mm
0.641 Ω/km
660 kg/km
A
Current Carrying Capacity in Air
168 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
4x70 mm²
32 mm
0.443 Ω/km
940 kg/km
A
Current Carrying Capacity in Air
213 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
4x95 mm²
36 mm
0.32 Ω/km
1270 kg/km
A
Current Carrying Capacity in Air
258 A
Conductor Structure
Stranded Aluminum (Class 2)
Test Voltage (AC)
4000 VAC
Insulation
XLPE
Current Type
AC
Minimum Bending Radius
12 x D mm
Temperature Range
90 °C
Minimum Installation Temperature
5 °C
Short Circuit Temperature
250 °C
Standard
NFC 33-209
Flame Retardant Test
IEC 60332-1
Title Type Language
ABC (NFC) Ürün Ana Görseli PNG
ABC (NFC) Ürün Kataloğu PDF
ABC (NFC) Ürün Kataloğu PDF
ABC (NFC) Ürün Kesit Görseli JPG