AAC (ASTM)

All Aluminium Conductors
Pure Aluminum Conductors are manufactured according to TS EN 50182 standards. Conductors are stranded concentrically in seven or more layers. If the conductor consists of multiple layers, adjacent layers are stranded in opposite directions. Production can be made according to DIN, BS, ASTM, CSA, NF, EN standards upon request. Used in low voltage distribution lines.

Twisted
Technical Specifications
Product
Arbustus (402,8 mm²)
26.04 mm
0.0715 Ω/km
1109 kg/km
A
Current Carrying Capacity in Air
878 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 3,72 ad-mm
Current Type
AC
Actual Code (New Standard)
Arbustus
Standard
ASTM
Aster (67,4 mm²)
10.5 mm
0.4276 Ω/km
185.7 kg/km
A
Current Carrying Capacity in Air
286 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
7 / 3,50 ad-mm
Current Type
AC
Actual Code (New Standard)
Aster
Standard
ASTM
Bitterroot (1393 mm²)
48.62 mm
0.0209 Ω/km
3872 kg/km
A
Current Carrying Capacity in Air
1793 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
91 / 4,42 ad-mm
Current Type
AC
Actual Code (New Standard)
Bitterroot
Standard
ASTM
Bluebell (523,7 mm²)
29.75 mm
0.055 Ω/km
1441 kg/km
A
Current Carrying Capacity in Air
1031 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 4,25 ad-mm
Current Type
AC
Actual Code (New Standard)
Bluebell
Standard
ASTM
Bluebonnet (1773 mm²)
54.86 mm
0.0166 Ω/km
4977 kg/km
A
Current Carrying Capacity in Air
2024 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
127 / 4,22 ad-mm
Current Type
AC
Actual Code (New Standard)
Bluebonnet
Standard
ASTM
Camellia (506,7 mm²)
29.25 mm
0.0596 Ω/km
1394 kg/km
A
Current Carrying Capacity in Air
1010 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 3,25 ad-mm
Current Type
AC
Actual Code (New Standard)
Camellia
Standard
ASTM
Canna (201,4 mm²)
18.35 mm
0.1432 Ω/km
554.9 kg/km
A
Current Carrying Capacity in Air
570 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 3,67 ad-mm
Current Type
AC
Actual Code (New Standard)
Canna
Standard
ASTM
Carnation (725,1 mm²)
35.01 mm
0.0398 Ω/km
1997 kg/km
A
Current Carrying Capacity in Air
1253 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 3,89 ad-mm
Current Type
AC
Actual Code (New Standard)
Carnation
Standard
ASTM
Cattail (380 mm²)
25.38 mm
0.0759 Ω/km
1046 kg/km
A
Current Carrying Capacity in Air
847 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 2,82 ad-mm
Current Type
AC
Actual Code (New Standard)
Cattail
Standard
ASTM
Cockscomb (456 mm²)
27.72 mm
0.0632 Ω/km
1256 kg/km
A
Current Carrying Capacity in Air
948 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 3,96 ad-mm
Current Type
AC
Actual Code (New Standard)
Cockscomb
Standard
ASTM
Columbine (694,8 mm²)
34.02 mm
0.0421 Ω/km
1884 kg/km
A
Current Carrying Capacity in Air
1212 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 3,78 ad-mm
Current Type
AC
Actual Code (New Standard)
Columbine
Standard
ASTM
Coreopsis (805,7 mm²)
36.9 mm
0.0358 Ω/km
2216 kg/km
A
Current Carrying Capacity in Air
1333 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 4,10 ad-mm
Current Type
AC
Actual Code (New Standard)
Coreopsis
Standard
ASTM
Cosmos (242 mm²)
20.1 mm
0.1193 Ω/km
664.8 kg/km
A
Current Carrying Capacity in Air
639 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 4,02 ad-mm
Current Type
AC
Actual Code (New Standard)
Cosmos
Standard
ASTM
Cowslip (1013 mm²)
41.47 mm
0.0284 Ω/km
2787 kg/km
A
Current Carrying Capacity in Air
1518 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
91 / 3,77 ad-mm
Current Type
AC
Actual Code (New Standard)
Cowslip
Standard
ASTM
Daffodil (177,3 mm²)
17.25 mm
0.1625 Ω/km
487.9 kg/km
A
Current Carrying Capacity in Air
526 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 3,45 ad-mm
Current Type
AC
Actual Code (New Standard)
Daffodil
Standard
ASTM
Dahlia (282 mm²)
21.75 mm
0.1023 Ω/km
775.8 kg/km
A
Current Carrying Capacity in Air
703 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 4,35 ad-mm
Current Type
AC
Actual Code (New Standard)
Dahlia
Standard
ASTM
Daisy (135,2 mm²)
14.88 mm
0.2133 Ω/km
372.3 kg/km
A
Current Carrying Capacity in Air
443 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
7 / 4,96 ad-mm
Current Type
AC
Actual Code (New Standard)
Daisy
Standard
ASTM
Flag (354,7 mm²)
24.48 mm
0.0813 Ω/km
975.8 kg/km
A
Current Carrying Capacity in Air
812 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 2,72 ad-mm
Current Type
AC
Actual Code (New Standard)
Flag
Standard
ASTM
Gladiolus (765,41 mm²)
36 mm
0.0376 Ω/km
2108 kg/km
A
Current Carrying Capacity in Air
1294 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 4,00 ad-mm
Current Type
AC
Actual Code (New Standard)
Gladiolus
Standard
ASTM
Goldenrod (483,4 mm²)
28.62 mm
0.0596 Ω/km
1331 kg/km
A
Current Carrying Capacity in Air
982 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 3,18 ad-mm
Current Type
AC
Actual Code (New Standard)
Goldenrod
Standard
ASTM
Goldentuft (228 mm²)
19.55 mm
0.1264 Ω/km
627.6 kg/km
A
Current Carrying Capacity in Air
616 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 3,91 ad-mm
Current Type
AC
Actual Code (New Standard)
Goldentuft
Standard
ASTM
Hawkweed (506,7 mm²)
29.26 mm
0.0596 Ω/km
1395 kg/km
A
Current Carrying Capacity in Air
1010 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 4,18 ad-mm
Current Type
AC
Actual Code (New Standard)
Hawkweed
Standard
ASTM
Hawthorn (604,2 mm²)
31.95 mm
0.0447 Ω/km
1662 kg/km
A
Current Carrying Capacity in Air
1124 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 3,55 ad-mm
Current Type
AC
Actual Code (New Standard)
Hawthorn
Standard
ASTM
Heuchera (329,4 mm²)
23.59 mm
0.0875 Ω/km
907.4 kg/km
A
Current Carrying Capacity in Air
775 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 3,37 ad-mm
Current Type
AC
Actual Code (New Standard)
Heuchera
Standard
ASTM
Hyacinth (253,3 mm²)
20.65 mm
0.1137 Ω/km
696.8 kg/km
A
Current Carrying Capacity in Air
658 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 2,95 ad-mm
Current Type
AC
Actual Code (New Standard)
Hyacinth
Standard
ASTM
Iris (33,6 mm²)
7.41 mm
0.8574 Ω/km
92.6 kg/km
A
Current Carrying Capacity in Air
185 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
7 / 2,47 ad-mm
Current Type
AC
Actual Code (New Standard)
Iris
Standard
ASTM
Jessamine (886,7 mm²)
38.7 mm
0.0325 Ω/km
2442 kg/km
A
Current Carrying Capacity in Air
1408 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 4,30 ad-mm
Current Type
AC
Actual Code (New Standard)
Jessamine
Standard
ASTM
Larkspur (523,7 mm²)
29.79 mm
0.055 Ω/km
1442 kg/km
A
Current Carrying Capacity in Air
1031 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 3,31 ad-mm
Current Type
AC
Actual Code (New Standard)
Larkspur
Standard
ASTM
Laurel (135,2 mm²)
15.05 mm
0.2133 Ω/km
372.2 kg/km
A
Current Carrying Capacity in Air
443 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 3,10 ad-mm
Current Type
AC
Actual Code (New Standard)
Laurel
Standard
ASTM
Lilac (402,8 mm²)
26.1 mm
0.0715 Ω/km
1110 kg/km
A
Current Carrying Capacity in Air
878 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 2,90 ad-mm
Current Type
AC
Actual Code (New Standard)
Lilac
Standard
ASTM
Lupine (1267 mm²)
46.31 mm
0.023 Ω/km
3519 kg/km
A
Current Carrying Capacity in Air
1706 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
91 / 4,21 ad-mm
Current Type
AC
Actual Code (New Standard)
Lupine
Standard
ASTM
Magnolia (483,4 mm²)
28.56 mm
0.0596 Ω/km
1331 kg/km
A
Current Carrying Capacity in Air
982 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 4,08 ad-mm
Current Type
AC
Actual Code (New Standard)
Magnolia
Standard
ASTM
Marigold (564 mm²)
30.87 mm
0.0511 Ω/km
1553 kg/km
A
Current Carrying Capacity in Air
1079 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 3,43 ad-mm
Current Type
AC
Actual Code (New Standard)
Marigold
Standard
ASTM
Meadowswe (304 mm²)
22.61 mm
0.0948 Ω/km
836.3 kg/km
A
Current Carrying Capacity in Air
738 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 3,23 ad-mm
Current Type
AC
Actual Code (New Standard)
Meadowswe
Standard
ASTM
Mistletoe (282 mm²)
21.84 mm
0.1023 Ω/km
775.7 kg/km
A
Current Carrying Capacity in Air
704 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 3,12 ad-mm
Current Type
AC
Actual Code (New Standard)
Mistletoe
Standard
ASTM
Narcissus (644,5 mm²)
33.03 mm
0.0447 Ω/km
1774 kg/km
A
Current Carrying Capacity in Air
1169 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 3,67 ad-mm
Current Type
AC
Actual Code (New Standard)
Narcissus
Standard
ASTM
Nasturtium (362,6 mm²)
24.75 mm
0.0795 Ω/km
998.5 kg/km
A
Current Carrying Capacity in Air
823 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 2,75 ad-mm
Current Type
AC
Actual Code (New Standard)
Nasturtium
Standard
ASTM
Orchid (323,3 mm²)
23.31 mm
0.0893 Ω/km
886.9 kg/km
A
Current Carrying Capacity in Air
765 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 3,33 ad-mm
Current Type
AC
Actual Code (New Standard)
Orchid
Standard
ASTM
Oxlip (107,2 mm²)
13.26 mm
0.2688 Ω/km
295.2 kg/km
A
Current Carrying Capacity in Air
383 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
7 / 4,42 ad-mm
Current Type
AC
Actual Code (New Standard)
Oxlip
Standard
ASTM
Pansy (42,4 mm²)
8.34 mm
0.6801 Ω/km
116.6 kg/km
A
Current Carrying Capacity in Air
214 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
7 / 2,78 ad-mm
Current Type
AC
Actual Code (New Standard)
Pansy
Standard
ASTM
Peony (152 mm²)
15.95 mm
0.1896 Ω/km
418.3 kg/km
A
Current Carrying Capacity in Air
478 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 3,19 ad-mm
Current Type
AC
Actual Code (New Standard)
Peony
Standard
ASTM
Petunia (380 mm²)
25.34 mm
0.0759 Ω/km
1046 kg/km
A
Current Carrying Capacity in Air
847 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 3,62 ad-mm
Current Type
AC
Actual Code (New Standard)
Petunia
Standard
ASTM
Phlox (85 mm²)
11.79 mm
0.339 Ω/km
233.9 kg/km
A
Current Carrying Capacity in Air
331 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
7 / 3,93 ad-mm
Current Type
AC
Actual Code (New Standard)
Phlox
Standard
ASTM
Poppy (53,5 mm²)
9.36 mm
0.539 Ω/km
147.2 kg/km
A
Current Carrying Capacity in Air
247 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
7 / 3,12 ad-mm
Current Type
AC
Actual Code (New Standard)
Poppy
Standard
ASTM
Rose (21,1 mm²)
5.88 mm
1.362 Ω/km
58.2 kg/km
A
Current Carrying Capacity in Air
138 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
7 / 1,96 ad-mm
Current Type
AC
Actual Code (New Standard)
Rose
Standard
ASTM
Sagebrush (1140 mm²)
43.89 mm
0.0255 Ω/km
3166 kg/km
A
Current Carrying Capacity in Air
1612 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
91 / 3,99 ad-mm
Current Type
AC
Actual Code (New Standard)
Sagebrush
Standard
ASTM
Snapdragon (456 mm²)
27.81 mm
0.0632 Ω/km
1256 kg/km
A
Current Carrying Capacity in Air
948 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
61 / 3,09 ad-mm
Current Type
AC
Actual Code (New Standard)
Snapdragon
Standard
ASTM
Sneezewort (126,7 mm²)
14.4 mm
0.2275 Ω/km
348.8 kg/km
A
Current Carrying Capacity in Air
425 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
7 / 4,80 ad-mm
Current Type
AC
Actual Code (New Standard)
Sneezewort
Standard
ASTM
Syringa (242 mm²)
20.16 mm
0.1193 Ω/km
664.8 kg/km
A
Current Carrying Capacity in Air
639 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 2,88 ad-mm
Current Type
AC
Actual Code (New Standard)
Syringa
Standard
ASTM
Trillium (1520 mm²)
50.7 mm
0.0191 Ω/km
4226 kg/km
A
Current Carrying Capacity in Air
1874 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
127 / 3,90 ad-mm
Current Type
AC
Actual Code (New Standard)
Trillium
Standard
ASTM
Tulip (170,5 mm²)
16.9 mm
0.1695 Ω/km
469.5 kg/km
A
Current Carrying Capacity in Air
513 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 3,38 ad-mm
Current Type
AC
Actual Code (New Standard)
Tulip
Standard
ASTM
Valerian (126,7 mm²)
14.55 mm
0.2275 Ω/km
348.6 kg/km
A
Current Carrying Capacity in Air
425 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 2,91 ad-mm
Current Type
AC
Actual Code (New Standard)
Valerian
Standard
ASTM
Varbena (354,7 mm²)
24.43 mm
0.0813 Ω/km
975.7 kg/km
A
Current Carrying Capacity in Air
812 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 3,49 ad-mm
Current Type
AC
Actual Code (New Standard)
Varbena
Standard
ASTM
Violet (362,6 mm²)
24.71 mm
0.0795 Ω/km
998.5 kg/km
A
Current Carrying Capacity in Air
823 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
37 / 3,53 ad-mm
Current Type
AC
Actual Code (New Standard)
Violet
Standard
ASTM
Zinnia (253,3 mm²)
20.6 mm
0.1137 Ω/km
697.1 kg/km
A
Current Carrying Capacity in Air
658 A
Conductor Structure
Stranded Aluminum (Class 2)
Number and Wire Diameter (Conductor)
19 / 4,12 ad-mm
Current Type
AC
Actual Code (New Standard)
Zinnia
Standard
ASTM
Title Type Language
AAC (ASTM) Ürün Alternatif Görseli PNG
AAC (ASTM) Ürün Ana Görseli PNG
AAC (ASTM) Ürün Kataloğu PDF
AAC (ASTM) Ürün Kataloğu PDF
AAC (ASTM) Ürün Kataloğu PDF
AAC (ASTM) Ürün Kesit Görseli JPG
AAC (ASTM) CE Kalite Sertifikası PDF
AAC (ASTM) TSE Kalite Sertifikası PDF
How can we help you?
Or
Adobestock 558884015 1